background image

 

 

 

 

Technical Bulletin  

 

SuperDuct Conventional Two-Wire Duct Smoke Detector 

Model Description 

SD-MAG 

Test magnet kit 

SD-VTK 

Air velocity test kit 

Operation 

Controls and indicators 

Magnetic

test

switch

Alarm

Trouble

Dirty

 

Figure 3: Duct smoke detector controls and indicators 

The controls and indicators on the duct smoke detector (see 
Figure 3) are as follows: 
 

Control or indicator 

Description 

Magnetic test switch 

Used to alarm test the detector, 
determine its dirty level, and 
determine if the detector is in the 
trouble state 

Alarm LED 

Indicates the detector is in the alarm 
state 

Trouble LED 

Flashes once to indicate the detector 
is in the trouble state. Requires 
manual activation from user. 

Dirty LED 

Flashes 1 to 4 times to indicate the 
detector’s dirtiness level. Requires 
manual activation from user. 

Normal state 

The duct smoke detector operates in the normal state in the 
absence of any trouble conditions and when its sensing 
chamber is free of smoke or an alarm test is initiated.  

Alarm state 

The duct smoke detector enters the alarm state (is activated) 
when the amount of smoke in its sensing chamber exceeds its 
alarm threshold setting or when an alarm test is initiated. Upon 
entering the alarm state, the duct smoke detector’s: 

• 

Alarm LED turns on 

• 

Common alarm relay contact switches position 

• 

Remote alarm LED output turns on (is activated) 

In addition, the duct smoke detector places a low impedance 
short across the initiating device circuit. The low impedance 
short causes the control panel’s IDC input to generate an 
alarm or supervisory event message depending on the device 
type with which it is configured. 

Trouble state 

The duct smoke detector enters the trouble state under the 
following conditions: 

• 

Its cover is removed and 20 minutes pass before it is 
properly secured 

• 

Its environmental compensation limit is reached 

• 

The detector is 100% dirty 

• 

An internal detector fault is present  

The duct smoke detector does not automatically indicate 
trouble conditions. Instead, you must test whether a trouble is 
present. For more information, see “Troubleshooting.” 

Note: 

All troubles are latched by the duct smoke detector. You 

must clear the trouble condition then reset the control panel in 
order to restore the detector to its normal state. 

Installation 

Installation guidelines 

To ensure correct operation, install the duct detector using the 
following guidelines: 

• 

Locate the detector so its sampling tube is positioned in a 
straight length of square duct between six and ten duct 
widths from any bends or obstructions as shown in the 
diagram below. See Figure 7 for detector dimensions. 

Содержание SuperDuct ESD-2W

Страница 1: ...ation and maintenance of duct smoke detectors is provided in the following standards NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 90A Installation of Air Conditioning and Ven...

Страница 2: ...is directed back into the ventilation system through an exhaust tube The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber When a sufficient amount of...

Страница 3: ...limited Quantity 1 Type Form C Ratings 2 0 A at 30 Vdc resistive Detector operating voltage 16 to 30 Vdc Detector operating current Startup 200 A Standby 70 A Alarm 5 to 100 mA Alarm impedance 50 to 7...

Страница 4: ...the alarm state the duct smoke detector s Alarm LED turns on Common alarm relay contact switches position Remote alarm LED output turns on is activated In addition the duct smoke detector places a low...

Страница 5: ...2 Drill the mounting holes using the drill template provided 3 Assemble the detector 4 Mount the detector on the HVAC duct 5 Verify the detector pressure differential Installing the sampling tube fro...

Страница 6: ...nished testing the duct smoke detector reset the control panel in order to restore the detector to its normal state Troubleshooting You can troubleshoot problems while the duct smoke detector is in op...

Страница 7: ...r 1 Remove the detector s cover then power down the detector by disconnecting the initiating device circuit wiring 2 Using a vacuum cleaner clean compressed air or a soft bristle brush remove loose di...

Страница 8: ...nventional Two Wire Duct Smoke Detector 8 70 in 22 1 cm 7 75 in 19 7 cm 8 15 in 20 7 cm 2 28 in 5 78 cm 5 45 in 13 84 cm 5 40 in 13 72 cm 1 38 in 3 51 cm 1 90 in 4 83 cm 3 08 in 7 82 cm 1 60 in 4 06 c...

Страница 9: ...vice on the same circuit is activated 1 2 3 4 Alarm SD TRK or SD TRM 2 Figure 8 Installation wiring diagram IDC short circuit current 100 mA 6 5 11 12 14 13 15 16 17 10 8 Auxiliary equipment CAUTION D...

Страница 10: ...Technical Bulletin 10 SuperDuct Conventional Two Wire Duct Smoke Detector...

Отзывы: