background image

 

 

 

 

Technical Bulletin  

 

SuperDuct Conventional Two-Wire Duct Smoke Detector 

Wiring 

Figure 8 and Figure 9 show how to wire the duct smoke 
detector and its accessories. The duct smoke detector’s IDC 
wiring differs depending on the control panel’s short circuit 
current specification. Run all field wiring into the detector 
through the knockouts located at the top of the detector 
housing. 

Caution: 

Incorrectly wiring the duct smoke detector to the 

control panel’s IDC circuit can damage the equipment. 

Maintenance and service 

Recommended service schedule 

Perform a visual inspection upon installation and once every 
six months thereafter. 

Perform an alarm test upon installation and once every twelve 
months thereafter. 

Testing the duct smoke detector 

Before testing the duct smoke detector, notify the proper 
authorities that the system is undergoing maintenance and, 
unless part of the test, disconnect all auxiliary equipment from 
its common alarm relay contacts. 

Note: 

You can’t initiate an alarm test if the duct smoke 

detector is in the trouble state.  

To test the duct smoke detector’s ability to report an alarm 
condition: 

• 

Using an SD-MAG, hold the SD-MAG where indicated 
on the side of the duct smoke detector for more than 5 
seconds 

• 

Using an SD-TRK, turn the key switch to the TEST 
position for more than 5 seconds 

• 

Using an SD-TRM, hold the SD-MAG test magnet to the 
target area for more than 5 seconds 

Once activated, verify the following: 

• 

The detector’s Alarm LED is on 

• 

If connected, the Alarm LED on the remote test station or 
LED indicator is on 

• 

The appropriate event message or visual indication is 
reported on the fire alarm control panel 

After you have finished testing the duct smoke detector, reset 
the control panel in order to restore the detector to its normal 
state. 

Troubleshooting 

You can troubleshoot problems while the duct smoke detector 
is in operation. However, be careful not to place the duct 
smoke detector in the alarm state since the procedure for 
troubleshooting and alarming the detector is similar.  

Caution: 

Before troubleshooting the duct smoke detector, 

notify the proper authorities that the fire alarm system is 
undergoing maintenance and take steps to prevent the control 
panel from responding to a false alarm. 

To test whether a trouble is present: 

• 

Using an SD-MAG, hold the SD-MAG where indicated 
on the side of the duct smoke detector for 1 to 4 seconds 

• 

Using an SD-TRK, turn the key switch to the TEST 
position for 1 to 4 seconds 

• 

Using an SD-TRM, hold the SD-MAG test magnet to the 
target area for 1 to 4 seconds 

If a trouble exists, the duct smoke detector’s Trouble LED will 
flash once. The most common troubles are described below. 
 

Problem Solution 

The cover is not properly 
secured 

Make sure the cover is 
attached and secured properly 
then reset the control panel 

The detector is greater than 
100% dirty 

Clean the duct smoke detector 
then reset the control panel 

Note:

 After correcting a problem, test the detector again to 

verify the problem was solved. 

 

If securing the cover and cleaning the detector did not fix the 
problem, you should replace the duct smoke detector’s printed 
circuit board (model number SD-2WPCB, ordered separately.) 

If the duct smoke detector is normal (not in trouble), the Dirty 
LED flashes as shown below.  
 

Flashes Description 

0 to 24% dirty (typical on a newly installed duct 
smoke detector) 

25 to 49% dirty 

50 to 74% dirty 

75 to 99% dirty 

 

Cleaning the duct smoke detector  

Clean the duct smoke detector when it becomes 75% to 99% 
dirty or sooner if conditions warrant. 

Содержание SuperDuct ESD-2W

Страница 1: ...ation and maintenance of duct smoke detectors is provided in the following standards NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 90A Installation of Air Conditioning and Ven...

Страница 2: ...is directed back into the ventilation system through an exhaust tube The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber When a sufficient amount of...

Страница 3: ...limited Quantity 1 Type Form C Ratings 2 0 A at 30 Vdc resistive Detector operating voltage 16 to 30 Vdc Detector operating current Startup 200 A Standby 70 A Alarm 5 to 100 mA Alarm impedance 50 to 7...

Страница 4: ...the alarm state the duct smoke detector s Alarm LED turns on Common alarm relay contact switches position Remote alarm LED output turns on is activated In addition the duct smoke detector places a low...

Страница 5: ...2 Drill the mounting holes using the drill template provided 3 Assemble the detector 4 Mount the detector on the HVAC duct 5 Verify the detector pressure differential Installing the sampling tube fro...

Страница 6: ...nished testing the duct smoke detector reset the control panel in order to restore the detector to its normal state Troubleshooting You can troubleshoot problems while the duct smoke detector is in op...

Страница 7: ...r 1 Remove the detector s cover then power down the detector by disconnecting the initiating device circuit wiring 2 Using a vacuum cleaner clean compressed air or a soft bristle brush remove loose di...

Страница 8: ...nventional Two Wire Duct Smoke Detector 8 70 in 22 1 cm 7 75 in 19 7 cm 8 15 in 20 7 cm 2 28 in 5 78 cm 5 45 in 13 84 cm 5 40 in 13 72 cm 1 38 in 3 51 cm 1 90 in 4 83 cm 3 08 in 7 82 cm 1 60 in 4 06 c...

Страница 9: ...vice on the same circuit is activated 1 2 3 4 Alarm SD TRK or SD TRM 2 Figure 8 Installation wiring diagram IDC short circuit current 100 mA 6 5 11 12 14 13 15 16 17 10 8 Auxiliary equipment CAUTION D...

Страница 10: ...Technical Bulletin 10 SuperDuct Conventional Two Wire Duct Smoke Detector...

Отзывы: