background image

 

 

 

 

Technical Bulletin  

 

SuperDuct Conventional Two-Wire Duct Smoke Detector 

environmental conditions. Hinged or removable service panels 
typically provide access to the equipment. 

The duct smoke detector’s primary purpose is to provide early 
warning of an impending fire and shut down the HVAC unit in 
order to prevent smoke from circulating throughout the 
building. It is typically used to detect smoke in the supply side 
of the HVAC system but can provide supervision of the return 
side as well (see Figure 1.) 

Return air

Remote

test

station

Duct smoke

detector

FACP

Rooftop HVAC unit

Supply air

Duct smoke

detector

HVAC

controls

Remote

test

station

 

Figure 1: Duct smoke detector application diagram 

WARNING: 

SuperDuct duct smoke detectors are not intended 

as substitutes for open area protection. 

Note: 

Install supply-side detectors at a point downstream from 

the supply fan and air filters and return-side detectors at a 
point before the return air is diluted by outside air.  

In installations where the duct smoke detector’s controls and 
indicators are hidden from view, a remote test station or an 
LED indicator can be connected to the detector to provide 
these functions. 

The duct smoke detector uses differential sensing to prevent 
gradual environmental changes from triggering false alarms. A 
rapid change in environmental conditions, such as smoke from 
a fire, causes the detector to automatically signal an alarm 
condition but dust and debris accumulated over time does not.  

Air is introduced to the duct smoke detector’s sensing 
chamber through a sampling tube that extends into the HVAC 

duct and is directed back into the ventilation system through 
an exhaust tube. The difference in air pressure between the 
two tubes pulls the sampled air through the sensing chamber. 
When a sufficient amount of smoke is detected in the sensing 
chamber, the duct smoke detector notifies the fire alarm 
control panel. 

Caution: 

Excess temperature differentials between the 

ambient air and the sampled air can produce unwanted 
condensation inside the detector, which may cause the detector 
to function improperly. Precautions should be taken to limit 
the temperature range and the amount of condensation to 
which the detector is exposed. 

Description 

The duct smoke detector (see Figure 2) comprises a plastic 
housing, a printed circuit board, a clear plastic cover, an 
exhaust tube, and a sampling tube. The exhaust tube and 
sampling tube are attached during installation. The sampling 
tube varies in length depending on the size of the HVAC duct 
and is ordered separately. 

The clear plastic cover permits visual inspections without 
having to disassemble the detector. The cover attaches to the 
detector housing using four captive screws and forms an 
airtight chamber around the sensing electronics. 

Features 

The duct smoke detector incorporates the following features: 

• 

Environmental compensation with differential sensing for 
reliable, stable, and drift-free sensitivity 

• 

Magnet-activated test switch  

• 

PCB mounted photoelectric detector with onboard 
intelligence 

• 

Cover tamper switch for added security 

• 

Sampling tube can be installed with or without the cover 
in place and can be rotated in 45-degree increments to 
ensure proper alignment with duct airflow 

• 

Alarm, Trouble, and Dirty status LEDs 

• 

Extended temperature and air velocity ranges 

• 

One Form C auxiliary alarm relay for controlling ancillary 
equipment (e.g., HVAC controls) 

Содержание SuperDuct ESD-2W

Страница 1: ...ation and maintenance of duct smoke detectors is provided in the following standards NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 90A Installation of Air Conditioning and Ven...

Страница 2: ...is directed back into the ventilation system through an exhaust tube The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber When a sufficient amount of...

Страница 3: ...limited Quantity 1 Type Form C Ratings 2 0 A at 30 Vdc resistive Detector operating voltage 16 to 30 Vdc Detector operating current Startup 200 A Standby 70 A Alarm 5 to 100 mA Alarm impedance 50 to 7...

Страница 4: ...the alarm state the duct smoke detector s Alarm LED turns on Common alarm relay contact switches position Remote alarm LED output turns on is activated In addition the duct smoke detector places a low...

Страница 5: ...2 Drill the mounting holes using the drill template provided 3 Assemble the detector 4 Mount the detector on the HVAC duct 5 Verify the detector pressure differential Installing the sampling tube fro...

Страница 6: ...nished testing the duct smoke detector reset the control panel in order to restore the detector to its normal state Troubleshooting You can troubleshoot problems while the duct smoke detector is in op...

Страница 7: ...r 1 Remove the detector s cover then power down the detector by disconnecting the initiating device circuit wiring 2 Using a vacuum cleaner clean compressed air or a soft bristle brush remove loose di...

Страница 8: ...nventional Two Wire Duct Smoke Detector 8 70 in 22 1 cm 7 75 in 19 7 cm 8 15 in 20 7 cm 2 28 in 5 78 cm 5 45 in 13 84 cm 5 40 in 13 72 cm 1 38 in 3 51 cm 1 90 in 4 83 cm 3 08 in 7 82 cm 1 60 in 4 06 c...

Страница 9: ...vice on the same circuit is activated 1 2 3 4 Alarm SD TRK or SD TRM 2 Figure 8 Installation wiring diagram IDC short circuit current 100 mA 6 5 11 12 14 13 15 16 17 10 8 Auxiliary equipment CAUTION D...

Страница 10: ...Technical Bulletin 10 SuperDuct Conventional Two Wire Duct Smoke Detector...

Отзывы: