E-HD Fixed-Temperature/Rate-of-Rise Heat 
Detector Installation Sheet 

Operation 

The E-HD Fixed-Temperature/Rate-of-Rise Heat Detector can 
be configured as a rate-of-rise detector (default) or, through 
programming, as a fixed-temperature heat detector. When 
configured as a rate-of-rise detector, a rate-of-rise heat sensor 
can quickly detect a fast, flaming fire. When configured as a 
fixed-temperature heat detector, a fixed-temperature heat 
sensor monitors the temperature of the air in its surroundings 
and determines whether to initiate an alarm. The detector is 
capable of performing comprehensive self-diagnostics and 
storing the results. 

LED operation 

The detector provides a bicolor LED that shows its status. 

Normal: Green LED flashes 

Alarm/active: Red LED flashes 

Installation 

Refer to 

Edwards Signaling Smoke and Heat Detector 

Application Bulletin 

(P/N 3101212) for additional information on 

detector placement and spacing. 

WARNINGS

 

• 

This detector does not operate without electrical power. As 
fires frequently cause power interruption, discuss further 
safeguards with the local fire protection specialist. 

• 

This detector does not sense fires that start in areas 
where heat cannot reach the detector. Heat from fires in 
walls, roofs, or on the opposite side of closed doors may 
not reach the detector. 

• 

This detector is intended for use with ionization and/or 
photoelectric smoke detectors. The heat detector by itself 
does not provide life safety protection. 

• 

This detector does not detect oxygen levels, smoke, toxic 
gases, or flames. Use this device only as part of a broad-
based, life-safety program which includes a variety of 
information sources pertaining to heat and smoke levels, 
extinguishment systems, visual and audible devices, and 
other safety measures. 

• 

Independent studies recommend using heat detectors only 
for property protection. Never rely on heat detectors as the 
sole means of fire protection. 

• 

To ensure proper operation, schedule maintenance 
(regular or selected) in accordance with the requirements 
of the authority having jurisdiction. Refer to NFPA 72 and 

CAN/ULC−S536. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to 
room temperature before applying power. 

• 

Keep the dust cover (supplied) on the detector during 
installation and remove it prior to commissioning and 
service. The dust cover is not a substitute for removing the 
detector during new construction or heavy remodeling. 

To install the detector: 

1.  Install and wire the detector base using the installation 

sheet supplied with the detector base. 

2.  Set the detector address. Refer to the panel technical 

reference manual for a list of valid addresses.  

Use a screwdriver to adjust the two rotary switches on the 
back of the detector. Set the left rotary switch (0 through 
12) for the 10s and 100s digit and the right rotary switch 
for the 0 through 9 digit. 

3.  Connect the detector to the base by rotating the detector 

clockwise until it snaps into the locked position. 

The head can be removed by turning it counterclockwise. 

4.  If the head must lock to the base, break away the locking 

tab using a pair of pliers. 

To then remove the detector head after breaking away the 
locking tab, insert a small screwdriver into the slot on the 
side of the base and press in while simultaneously turning 
the detector head counterclockwise. 

Figure 1: Setting detector address (address 32 shown) 

 

1. 

Insert screwdriver here 

 