1. 

Breakaway tab 

Test 

NFPA 72 and CAN/ULC S537 require a calibrated sensitivity 
test upon completion of the original installation and following 
any modifications or additions to the system. The detector can 
perform this test and generate a system sensitivity report. 

To test the detector: 

1.  Before initial testing, remove the dust cover from the 

detector and notify the proper authorities that the fire 
alarm system is undergoing maintenance and will be 
temporarily out of service. 

2.  Test the detector for proper operation using a heat gun 

maintaining a six-inch minimum distance. Use caution as 
excess heat can damage the detector and detector 
housing. 

Specifications 

 

Communication line voltage 

Maximum 20 V peak-to-peak 

Normal operating current 

45 µA 

Alarm current 

45 µA 

UL/ULC fixed-temp alarm rating 

135°F (57°C) 

Actual alarm point 

130 to 140°F (54 to 60°C) 

Rate-of-rise 

15°F (8°C)/min. 

Compatible bases 

Standard: B4U, B4U-LP 
Relay: RB4U 
Isolator: IB4U 
Audible: SB4U 

Maximum spacing 

50 ft. (15 m) centers 

Maximum distance from ceiling 
wall-mounted 

12 in. (305 mm) 

Storage temperature 

−4 to 140°F (−20 to 60°C) 

Operating environment 
 

Temperature 

 

Humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% RH, noncondensing at 
90°F (32°C) 

Certification and compliance 

 

Manufacturer 

Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 34202, 
USA 

Year of 
manufacture 

The first two digits of the date code (located on the 
product identification label) are the year of 
manufacture. 

North American 
standards 

Meets: UL 521, CAN/ULC-S530-M91,  
Follow: NFPA 72, CAN/ULC-S524 

Contact information 

For contact information, see our Web site: 
www.edwardssignaling.com. 

 