19
380V/3PH/60Hz
Model
06
12
18
Controls FLA
1.0
1.0
1.0
Fans FLA
1.6
2.8
3.8
Reheat FLA
8.2
8.2
13.2
Humidifier FLA
2.3
2.3
3.4
Max Unit FLA - Cooling only
2.6
3.8
4.8
Max Fuse FLA
10.0
10.0
10.0
Max Unit FLA - Cooling & Dehumidification
10.8
12.1
18.0
Max Fuse FLA
15.0
20.0
25.0
Max Unit FLA - Heating and Humidification
13.1
14.4
21.4
Max Fuse FLA
20.0
20.0
30.0
460V/3PH/60Hz
Model
06
12
18
Controls FLA
1.0
1.0
1.0
Fans FLA
1.3
2.3
3.1
Reheat FLA
10.1
10.1
16.0
Humidifier FLA
1.9
1.9
2.8
Max Unit FLA - Cooling only
2.3
3.3
4.1
Max Fuse FLA
10.0
10.0
10.0
Max Unit FLA - Cooling & Dehumidification
12.4
13.4
20.1
Max Fuse FLA
20.0
20.0
25.0
Max Unit FLA - Heating and Humidification
14.3
15.3
22.9
Max Fuse FLA
20.0
20.0
30.0
Notes:
1.
FLA = Full Load Amps.
2.
Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions.
3.
Max FLA of cooling only unit: FLA = Co Fans.
4.
Max FLA of unit with reheat in dehumidification: FLA = Co Fans + Reheat.
5.
Max FLA of units with heating & humidifiers: FLA = Co Fans + Humidifier.
6.
Max Fuse is the recommended value of the unit overcurrent protection device.
ELECTRICAL DETAILS – CHILLED WATER UNITS