18
400V/3PH/50Hz
Model
06
12
18
Controls FLA
1.0
1.0
1.0
Fans FLA
1.5
2.7
3.6
Reheat FLA
8.7
8.7
13.9
Humidifier FLA
2.2
2.2
3.2
Max Unit FLA - Cooling only
2.5
3.7
4.6
Max Fuse FLA
10 .0
10.0
10.0
Max Unit FLA - Cooling & Dehumidification
11.2
12.4
18.5
Max Fuse FLA
20.0
20.0
25.0
Max Unit FLA - Heating and Humidification
13.4
14.6
21.7
Max Fuse FLA
20.0
20.0
30.0
220V/3PH/60Hz
Model
06
12
18
Controls FLA
1.0
1.0
1.0
Fans FLA
2.7
4.9
6.6
Reheat FLA
15.8
15.8
25.3
Humidifier FLA
4.0
4.0
5.8
Max Unit FLA - Cooling only
3.7
5.9
7.6
Max Fuse FLA
10.0
15.0
20.0
Max Unit FLA - Cooling & Dehumidification
19.5
21.7
32.9
Max Fuse FLA
35.0
30.0
45.0
Max Unit FLA - Heating and Humidification
23.5
25.7
38.7
Max Fuse FLA
30.0
35.0
50.0
Notes:
1.
FLA = Full Load Amps.
2.
Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions.
3.
Max FLA of cooling only unit: FLA = Co Fans.
4.
Max FLA of unit with reheat in dehumidification: FLA = Co Fans + Reheat.
5.
Max FLA of units with heating & humidifiers: FLA = Co Fans + Humidifier.
6.
Max Fuse is the recommended value of the unit overcurrent protection device.
ELECTRICAL DETAILS – CHILLED WATER UNITS