17
380V/3PH/60Hz
Model
06
12
18
Controls FLA
1.0
1.0
1.0
Fans FLA
1.6
2.9
3.8
Reheat FLA
8.2
8.2
13.2
Humidifier FLA
2.3
2.3
3.4
Scroll Compressor FLA
3.6
6.2
8.3
Condenser FLA 30˚C
3.9
3.9
3.9
Condenser FLA 35˚C
3.9
3.9
3.9
Condenser FLA 40˚C
3.9
3.9
7.8
Condenser FLA 45˚C
3.9
7.8
7.8
Condenser FLA 50˚C
3.9
7.8
11.7
Max Unit FLA - Cooling only
10.1
17.9
24.8
Max Fuse FLA
15.0
30.0
35.0
Max Unit FLA - Cooling & Dehumidification
18.3
26.1
38.0
Max Fuse FLA
25.0
40.0
45.0
Max Unit FLA - Heating and Humidification
13.1
14.4
21.4
Max Fuse FLA
20.0
20.0
30.0
460V/3PH/60Hz
Model
06
12
18
Controls FLA
1.0
1.0
1.0
Fans FLA
1.3
2.3
3.1
Reheat FLA
10.1
10.1
16.1
Humidifier FLA
1.9
1.9
2.8
Scroll Compressor FLA
4.3
7.4
10.0
Condenser FLA 30˚C
1.2
1.2
1.2
Condenser FLA 35˚C
1.2
1.2
1.2
Condenser FLA 40˚C
1.2
1.2
2.4
Condenser FLA 45˚C
1.2
2.4
2.4
Condenser FLA 50˚C
1.2
2.4
3.6
Max Unit FLA - Cooling only
7.8
12.9
17.3
Max Fuse FLA
15.0
25.0
30.0
Max Unit FLA - Cooling & Dehumidification
17.7
22.8
33.2
Max Fuse FLA
30.0
35.0
50.0
Max Unit FLA - Heating and Humidification
14.3
15.3
23.0
Max Fuse FLA
20.0
25.0
40.0
Notes:
1.
FLA = Full Load Amps.
2.
Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions.
3.
Max FLA of cooling only unit: FLA = Co Fans + Comp Condenser.
4.
Max FLA of unit with reheat in dehumidification: FLA = Co Fans + Comp Condenser.
5.
Max FLA of units with heating & humidifiers: FLA = Co Fans + Humidifier.
6.
Max Fuse is the recommended value of the unit overcurrent protection device.
ELECTRICAL DETAILS – AIR COOLED UNITS