Calibrating the Field Unit
PhaseTrakker
AP30
18
The Calibration screen prompts you to place the Hotstick Unit on a known phase
A (0
°
). Good hotstick signal reception from a source with no interference from
adjacent phases will give the most accurate calibration. When the Hotstick Unit is
in position and the Field Unit displays a steady Hotstick light, press OK.
Important: If the Hotstick light on the Field Unit is unsteady (blinking
or flickering), inaccurate calibration may result. Reposition the Field
Unit and Hotstick Unit to obtain a steady Hotstick light.
Note: Once OK is pressed, calibration will proceed on any electric
fields sensed. If OK is pressed before the Hotstick Unit is in position,
move the Hotstick Unit quickly into place from a direction that
minimizes interference from adjacent phases.
Calibration to the configured Reference Unit(s) is automatically performed using
the first stable measurement. The parameters for a stable measurement (default
3 consecutive readings within 5
°
) can be changed using the PhaseTrakker Utility.