DA-Data Aggregator

®

 DA-400™ 

and 

iCITE 

® 

Installation Manual 

 

Eberle Design Inc. 

Page 

9

 

 

powered and that the processor and functionality is operational for the DA-400™. The other 

connectors can now be attached. No specific or particular connection order is required. 

3.4 INSTALLING THE DA-400™ ANTENNA / ANTENNA ASSEMBLY  

The next step is to install the 5-band antenna and Radome assembly. Now that the location 

for the DA-400™ has been established determine where the antenna will need to be 

mounted. If the antenna will be mounted on top of the cabinet use a step-down drill bit to 

drill the desired size hole to feed the mounting bolt through. For the 5-band antenna it will 

need to be a 1/2 in. (12.7mm) feed through hole. Feed the cables through the hole. Take 

care to ensure that no rough edges on the drilled hole cut the antenna cable shielding. 

Place the Radome firmly onto the cabinet. A small amount of silicone adhesive can be used 

to ensure a better seal. Then thread the cables through the provided cut out nut and 

washer inside the cabinet. Tighten the nut to secure the antenna Radome. Care should be 

taken to not drop the nut or washer inside the operational cabinet and ensure the antenna 

has been located in a position where the threaded connection will be accessible to your 

hand to place the nut and washer and have adequate room to use a wrench to tighten the 

nut. Pay special attention to any internal cabinet “voids” where metal has been folded and 

the antenna mount will not penetrate fully. Metal Epoxy Putty can be used if need to repair 

unwanted cabinet penetrations. It is recommended to utilize a cardboard box inside the 

cabinet to capture any metal drill shavings and prevent potential wiring shorts inside the 

cabinet. Drilling from the outside in provides an opportunity to capture the drill shavings. 

 

If the Radome cannot be mounted to the top of the cabinet a side mounted bracket is 

available for purchase. The feed hole will be drilled in the side of the cabinet and the 

bracket will be mounted to the side of the cabinet, where the mounting ears are located, if 

there are detachable mounting ears. Otherwise two smaller holes will need to be drilled for 

the attachment bolts. 

 

Once the antenna assembly is mounted, connect the GPS and the Cell leads to the DA-

400™. Each lead will be marked accordingly and will be found next to the SMA connector. 

At this time, the DSRC and Bluetooth leads can be left disconnected. It is recommended 

they are looped and tie-wrapped in an inconspicuous location inside the cabinet for future 

use. 

 

After the GPS and the cellular antenna are attached there will be a second indications on 

the front of the DA-400™. The LED marked HEART may take several minutes to light up, 

but once it lights up will it will begin to flash.

 

This is the indication that the Cellular modem 

has connected to the cloud based software, and reported the location of the DA-400™. 

 

NOTE:

 

The Antenna Radome Assembly and Harness Assemblies are sold separately. 

1

2

3

4

5

2.6

2.0

.49 in

11/16 in.

.84 in.

.5 in

Lead 1 – GPS – 1575.42 MHz – SMA-M

Lead 2 – Cell – Varies – SMA-M

Lead 3 – Wi-Fi – 2.4 GHz – SMA-RP

Lead 4 – BlueTooth – 2.4 GHz – SMA-M

Lead 5 – DSRC – 5.9 GHz – SMA-M

 

Figure 8 Five-Band Antenna 

Содержание iCITE DA-400

Страница 1: ...NTAINS IMPORTANT INSTALLATION INSTRUCTIONS iCITE Intelligent Cabinet Interface to Traffic Equipment REVISION 03 July 2019 Version 1 0 888 0400 001 iCITE DA Data Aggregator DA 400 Installation and Oper...

Страница 2: ...ment on the part of EDI EDI provides this document as is without warranty of any kind either expressed or implied including but not limited to its particular purpose EDI reserves the right to make imp...

Страница 3: ...t 12 3 10 Configuration Review 13 3 11 Changing Configurations 22 3 12 Local Website Settings 22 3 13 Network Settings 23 3 14 Update Frequency 25 3 15 Sync Pulse Settings 29 3 16 Utility Server Setti...

Страница 4: ...from the traffic controller cabinet and its associated components to an iCITE READY Web based user interface and display The local unit and web based configuration software is called iCITE G2 Intellig...

Страница 5: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 2 Figure 2 DA 400 Rear Panel View Connections...

Страница 6: ...figurations It will be up to the end user agency to determine the correct locations based on the implemented cabinet designs and the desired connectivity functionalities For those Agencies requiring s...

Страница 7: ...regator DA 400 and iCITE Installation Manual Eberle Design Inc Page 4 Figure 3 Optional Side Mount Antenna Mounting Bracket NOTE The DA 400 is ready to install out of the box Figure 4 DA 400 Front and...

Страница 8: ...ded due to the potential for water intrusion The unit should be placed in a location allowing air to circulate freely around it The leads for all wire harnesses are 8 feet 2 4 meters in length so the...

Страница 9: ...120 VDC 2 5 3 6 12 V VREF2 Input from detector output 16 A9 VREF2 RED 12 OR 24 VDC 0 62 VDC Reference pull up voltage for Detectors 9 16 A10 internally connected to logic ground A11 PED3 BLUE 0 28 VDC...

Страница 10: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 7 Figure 5 Typical Digital DC Input Figure 6 H 5 Connector Detector inputs Figure 7 H 7 Connector Inputs...

Страница 11: ...Typically used to measure the signal level for cabinet Flash B3 ANALOG DC 6 BLUE 0 30 VDC 0 42 VDC Typically used to measure the voltage on the Battery Backup on Batt signal B4 Temperature Sensor BLUE...

Страница 12: ...e fully Metal Epoxy Putty can be used if need to repair unwanted cabinet penetrations It is recommended to utilize a cardboard box inside the cabinet to capture any metal drill shavings and prevent po...

Страница 13: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 10 Figure 9 Five Band Antenna Specifications...

Страница 14: ...y range 3 6 CONNECTING A NEMA TS 2 TYPE 2 SDLC TO THE DA 400 If the DA 400 is being installed into a NEMA TS 2 Type 2 cabinet there is additional information that is relayed to the iCITE G2 software T...

Страница 15: ...urate and robust vehicle presence or count detection The information from the SDLC is sufficient for determining if detection is working and if traffic is flowing and daily trending capabilities howev...

Страница 16: ...able to Ethernet Port 1 on the DA 400 2 Configure your computer or laptop Network Adaptor to connect to the DA 400 with the network IP range of 192 168 1 XXX the DA 400 is 192 168 1 20 3 Open an Inter...

Страница 17: ...r DA 400 and iCITE Installation Manual Eberle Design Inc Page 14 c Network Settings ETH1 This will display the current network settings of ETH1 d Network Settings ETH2 This will display the current ne...

Страница 18: ...400 and iCITE Installation Manual Eberle Design Inc Page 15 e Network Settings Connection Priority This will show the order of connection priority f Network Settings DNS Settings This will show the D...

Страница 19: ...d iCITE Installation Manual Eberle Design Inc Page 16 g Network Settings NTP Server This will show the Network Time Protocol Settings h Network Settings Network APN This will show the Access Point Nam...

Страница 20: ...ual Eberle Design Inc Page 17 i Network Settings Update Frequency This will show the update frequency of various DA 400 configuration parameters j Network Settings Sync Pulse Settings This will show t...

Страница 21: ...lation Manual Eberle Design Inc Page 18 k Network Settings Utility Server Settings This will show the URL of the assigned Utility Server l Network Settings Monitor Settings This will show the IP addre...

Страница 22: ...and iCITE Installation Manual Eberle Design Inc Page 19 m Network Settings OpenVPN Settings This will show status of the OpenVPN setting n Network Settings Serial Port Settings This will show the sta...

Страница 23: ...A 400 and iCITE Installation Manual Eberle Design Inc Page 20 o Network Settings MQTT 1 This will show the associated MQTT Database Server Settings and configuration parameters p Logging In i Select C...

Страница 24: ...DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 21 ii Select Edit Configuration Radio Button Green Radio Button iii Enter Password Default Password is simplepass all low...

Страница 25: ...a Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 22 3 11 CHANGING CONFIGURATIONS a Main Page b Commit Changes Save Configuration 3 12 LOCAL WEBSITE SETTINGS a Listen Port b Cha...

Страница 26: ...llation Manual Eberle Design Inc Page 23 i Select Change Configuration Password Radio Button ii Enter New Password and Confirm iii Enter New Password again Confirm and select green Commit button 3 13...

Страница 27: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 24 b Static IP Selection c DHCP Selection d Network Settings Ethernet 2 See ETH1 for configuration options...

Страница 28: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 25 3 14 UPDATE FREQUENCY a Update Frequency AAC Voltage Change b Update Frequency AAC Min Time s...

Страница 29: ...gregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 26 c Update Frequency DAC Volt Change V d Update Frequency DAC Min Time s e Update Frequency Detector Min Time s f Update Frequency...

Страница 30: ...ITE Installation Manual Eberle Design Inc Page 27 g Update Frequency Cell Min Change h Update Frequency Cell Min RX TX Change i Update Frequency GPS Min Time s j Update Frequency GPS Min Change ft k U...

Страница 31: ...r DA 400 and iCITE Installation Manual Eberle Design Inc Page 28 l Update Frequency Temperature Min Change F m Update Frequency Wi Fi Min Time s n Update Frequency Monitor Min Time s o Update Frequenc...

Страница 32: ...n Manual Eberle Design Inc Page 29 3 15 SYNC PULSE SETTINGS a Sync Pulse Settings Select Sync Pulse Desired Time Zone b Select time for Sync Pulse to occur Enter using a 24 hour Clock Format Enter add...

Страница 33: ...400 and iCITE Installation Manual Eberle Design Inc Page 30 3 16 UTILITY SERVER SETTINGS a Utility Server Settings Utility Server URL b Utility Server Settings Service Key c Utility Server Settings Co...

Страница 34: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 31 3 17 MONITOR SETTINGS a Monitor Settings Enter IP Address of connected EDI or RAE IP enabled Signal Monitor...

Страница 35: ...2 3 18 MQTT SETTINGS a Add MQTT Server NOTE 1 Multiple MQTT Servers can be added and configured to the DA 400 NOTE 2 Be aware that adding remote MQTT broadcast reception servers will increase the DA 4...

Страница 36: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 33 d MQTT Settings Username e MQTT Settings Password f MQTT Settings Transport...

Страница 37: ...DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 34 g MQTT Settings QoS h MQTT Settings Message Format i MQTT Settings Auth Type j MQTT Settings Enable Cloud To Device me...

Страница 38: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 35 k MQTT Settings Cert Key File Choose File l MQTT Settings Save Configuration Changes...

Страница 39: ...E DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 36 3 19 OPENVPN SETTINGS a OpenVPN Settings Enable VPN True or False b OpenVPN Settings VPN Configuration File Choose F...

Страница 40: ...ator DA 400 and iCITE Installation Manual Eberle Design Inc Page 37 3 20 SERIAL PORT a Serial Port Settings Configured for None b Serial Port Settings External Monitor c Serial Port Settings Forwardin...

Страница 41: ...iCITE DA Data Aggregator DA 400 and iCITE Installation Manual Eberle Design Inc Page 38 e Forwarding Parity f Forwarding Baud g Forwarding Data Bits h Forwarding Stop Bits...

Страница 42: ...Design Inc Page 39 Section 4 MAINTENANCE 4 1 MAINTENANCE REQUIREMENTS Other than standard periodic preventative maintenance the traffic signal technician performs on the cabinet equipment there is no...

Страница 43: ...the Cell Antenna lead should provide an indication of the signal strength A number 5 or better should be indicated 0 being no signal and 9 being the strongest signal This will be equivalent to bars o...

Страница 44: ...deployment to ensure there is adequate cellular service coverage in the area the Data Aggregator will be installed 5 5 LED DISPLAY BLANK a Check the power outlet for 110VAC with your meter b Check th...

Страница 45: ...oken frayed or degraded with a visual inspection c Do not over tighten the connector 5 10 UNABLE TO CONNECT TO DATA AGGREGATOR VIA ETHERNET CONNECTION a Verify the Ethernet cable is not a crossover ca...

Отзывы: