13
E D G E I Q H A N D B O O K
the CT clamp around the AC wire that supplies the solar inverter on the installation. This is to monitor
the output of the solar inverter.
E. Install the modem into the USB socket. (Refer to Section 6. Communication Kit Installation for
instructions).
Note: Unlike active and neutral conductors, only
one
Earth wire is required for the EdgeIQ. Both may
be used if required as the two visible Earth terminals are electrically connected/bonded inside the unit.
If
only using one
Earth Terminal, ensure the screw is tightened on the terminal that is not in use.
Diagram 3: Wiring for Standard install, for switchboard main breaker 40/63A, see wiring diagram
section 4.1 and 4.2 on page 13 and 14.
Note: For a
Non-Standard install
, for switchboard main breaker of 80/100A, appropriate
wire sizing
should be installed in accordance to AS/NZS 3000 and AS/NZS 3008.
5.3. Conduit fitting
A. Select correct size gland or conduit adapter to the EdgeIQ. It is recommended:
For standard install of 16mm2 wire: Clipsal 263/32 conduit adapters with locking ring (in place of
the supplied glands)
(As an alternative, the nylon glands supplied with the unit will fit the existing knockout hole on the
EdgeIQ while allowing the 25mm conduit through the gland).
B. Use a nylon push rod (or similar) to help run the cables into the conduit.
C. Feed the cables with the nylon rod through the conduit.
D. Release the nylon push rod and fasten gland nut or conduit adaptor locking ring onto the conduit.
E. Run the wires into the EdgeIQ unit through the connector and then tighten the conduit socket
ensuring the gland gasket is installed correctly and the gland is not threaded.
F. The EdgeIQ must be installed after the main switch through a circuit breaker or fuse and must be
wired in accordance to current AS/NZS 3000:2007(Electrical Installation – Wiring Rules) and
AS/NZS 3008 (Electrical Installations – Selection of Cables)
All neutral wiring corresponds to
the size of the active conductor