Page 18 of 40
Function F07 Call List Priority & Rosters
The EDAC 400-02 can be programmed with up to 16 different phone numbers. By default the
programmed numbers are treated as a single list of 16 numbers. Using
F07
the list can be
divided up in to blocks of 4, or 8 and treated differently depending on the alarm Input trigger
number.
The list of telephone/pager numbers can be configured in a number of ways including rosters.
A roster is used to assign a specific call list to be used to call only the people who will be on duty
that day. You can use four separate lists of four phone numbers, and change which list is to be
used either remotely or on site.
When the call is established and the EDAC 400-02 is speaking the idle message, the current
roster may be changed by pressing
*
followed by the roster number (
1
,
2
,
3
or
4
).
07
1
= All Inputs use list 1 (
F11
to
F14
).
2
= All Inputs use list 2 (
F21
to
F24
).
3
= All Inputs use list 3 (
F31
to
F34
).
4
= All Inputs use list 4 (
F41
to
F44
).
5
= All Inputs use a combined 16 number list:
list 1, list 2, list 3 and then list 4.
6
= Each Input uses its own list. Calls are alternately
taken from each list in turn when more than one
Input is active.
7
= Inputs 1 & 2 use list 1 & 2. Inputs 3 & 4 use list 3 &
4 (two 8-number lists)
9
= Each Input uses its own list. Inputs with a lower
Input number are completed first.
Default: 5 (One list of 16 numbers)
Rosters 1-4