ECR International Dunkirk WPSB 3 Series Скачать руководство пользователя страница 29

29

APPENDIX A - CONTROL FUNCTION

 ECONOMY

 Target

 When the Economy feature is 

active, the Fuel Smart HydroStat continually sets 

target temperatures below the high limit setting  

to maximize fuel efficiency. When the boiler water 

reaches the target temperature, the LED illuminates 

and the burner will shut down. The boiler water will 

continue to circulate and heat the house as long as the 

thermostat call continues. The LED will stay lit until 

the boiler temperature drops below the differential set 

point at which point the boiler will be allowed to fire 

again. 

See Differential explanation on page 6 of Hydrolevel 

Manual. 

NOTE:

 This LED illuminates regularly during normal 

boiler operation

TEST/SETTINGS Button

To Test Low Water Cut-Off: Press and hold the Test/

Settings button for 5 seconds. The display will read 
LCO

.          LWCO TEST   LCO

 

The red Low Water light should illuminate and the 

burner circuit (B1 and B2) should de-energize.

 NOTE:

 

The control must be installed with a Hydrolevel Electro-

Well for low water cut-off functionality (see page 2 of 

Hydrolevel manual for more details).

To View Current Settings: 

Press and release the 

Test/Settings Button in short intervals to sequentially 

display the following settings:

 

          HIGH LIMIT SETTING 

HL

 LOW LIMIT SETTING 

LL

 ECONOMY SETTING 

ECO

     CURRENT TARGET TEMPERATURE 

000

The display will return to boiler temperature (default) if 

Test/Settings Button in not pressed for 5 seconds.

TEMP 

ACTIVE  

Indicates the Fuel Smart HydroStat 

control is powered and the temperature function is 

active.

TEMP 

HI TEMP 

Illuminates when the boiler water

temperature reaches the high limit setting. It will 

remain lit until the water temperature falls 10°. The 

Fuel SmartHydroStat prevents burner operation while 

this LED is on. See Differential explanation on page 6 

of Hydrolevel Manual.

LWCO 

ACTIVE

 Indicates the low water cut-off (LWCO) 

function of the Fuel Smart HydroStat is active. When 

the control is installed with a Hydrolevel Electro-Well, 

this LED will be on at all times when the control is 

powered.

IMPORTANT:

 If the control is installed with a well 

other than the Electro-Well, this LED will not illuminate 

indicating the control is not providing low water cut-off 

functionality.

LWCO

 LOW WATER

 Indicates the boiler is in a 

low water condition. The HydroStat control will 

prevent burner operation during this condition. If the 

LOW WATER light is blinking, the control has been 

programmed to provide lockout protection in the event 

a low water condition is detected. (see Manual Reset 

Low Water Cut-Off on page 8 of Hydrolevel manual). 

Pressing the TEST/SETTINGS button will reset the 

control.

IMPORTANT:

 The system must be checked by a 

qualified heating professional prior to resuming 

operation.

ECONOMY 

ACTIVE

 Indicates the Thermal Targeting 

function is active and the Fuel Smart HydroStat will 

reduce boiler temperature to conserve fuel. The 

Economy feature is activated using the ECONOMY dial.

 WARNING

Burn and scald hazard. Do not add water until boiler 

has fully cooled. Failure to follow these instructions 

could result in death or serious injury.

!

  

7

1

2

3

4

6

5

8

DAMPER POWER LED

Indicates the control is energizing the vent damper. 

For applications where the vent damper is not plugged 

into the HydroStat, the LED indicates the burner circuit 

(B1 - B2) is powered. LED will blink when power is sent 

to the Vent Damper and will turn solid when power 

returns from the end switch.

PN 240013090 REV. C [10/01/2021]

Содержание Dunkirk WPSB 3 Series

Страница 1: ...3D WPSB 3DP WPSB 4D WPSB 4DP WPSB 5D WPSB 5DP WPSB 6D WPSB 6DP WPSB 7D WPSB 7DP WPSB 8D WPSB 8DP WPSB 9D WPSB 9DP Tested For 50 psi ASME Working Pressure Manufactured by ECR International Inc 2201 Dwy...

Страница 2: ...n this manual in effect at the time of printing of this manual ECR International Inc reserves the right to discontinue change specifications or system design at any time without notice and without inc...

Страница 3: ...7 Vent Damper Operation 17 8 Gas Supply Piping 18 9 Electrical Wiring 19 10 Wiring Diagram 20 11 General Instructions 21 12 Lighting Instructions 22 13 Operating Your Boiler 23 14 Service Hints 26 15...

Страница 4: ...Dimensions 1 1 4 RETURN PN 240013090 REV C 10 01 2021 Dimensions BOILER MODEL NUMBER DIMENSIONS INCH Boiler Volume Gallon FLUE DIAMETER A WIDTH WPSB 3 5 11 3 30 WPSB 4 6 14 4 60 WPSB 5 6 17 6 00 WPSB...

Страница 5: ...and all requirements before beginning installation FOR YOUR SAFETY READ BEFORE OPERATING Hot Water Can Scald Water heated to temperature for clothes washing dish washing and other sanitizing needs can...

Страница 6: ...be found on the NIOSH website https www cdc gov niosh topics silica NIOSH approved respirators manufacturers and phone numbers are also listed on this website Wear long sleeved loose fitting clothing...

Страница 7: ...ting and other performance criteria with the gas manifold and control assembly on the boiler per the latest revision of ANSI Z21 13 CGA 4 9 5 Install boiler such that gas ignition system components ar...

Страница 8: ...oric acid muriatic acid Cements adhesives and glues Photo processing plants Garages with workshops Furniture refinishing areas and establishments Laundry Chemicals Laundry detergents bleaches fabric s...

Страница 9: ...iping Size and arrange discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate Run pipe as short and straight as possible t...

Страница 10: ...herwise damage and or malfunction could be caused Recommended water quality is o Hardness Less than 150 mg L o Acidity level 7 8 pH o Sediments Particle size less than 50 micron If the water quality i...

Страница 11: ...damage to boiler and venting system Minimum design return water temperature to prevent condensation in boiler and venting is 120 F Minimum high limit setting is 140 F 1 Boiler used in heating system w...

Страница 12: ...12 Figure 5 Chilled Water Piping Figure 4 Typical Hot Water Piping 4 CONNECTING SUPPLY AND RETURN PIPING CIRCULATOR PUMP PN 240013090 REV C 10 01 2021...

Страница 13: ...Bypass Piping Circulator On Supply Figure 7 Bypass Piping Circulator On Return Bypass Piping Required For High Mass Large Water Content Systems 4 CONNECTING SUPPLY AND RETURN PIPING PN 240013090 REV C...

Страница 14: ...60 Volume 21 ft3 ACH x Total Input Mbh C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces All Outdoor Air Provide permanent opening s communicating directly or...

Страница 15: ...ent pipe should have any dips or sags Requirements 3 Boiler series is classified as a Category I Vent installation shall be in accordance with Venting of Equipment of the National Fuel Gas Code ANSI Z...

Страница 16: ...ances remaining connected to it At time of removal of existing boiler following steps shall be followed with each appliance remaining connected to the common venting system placed in operation while o...

Страница 17: ...ition Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed in open position to permit burner o...

Страница 18: ...regulation should be used by propane installer Propane gas piping should be checked out by propane installer CHECKING GAS PIPING DANGER Fire Hazard Do not use matches candles open flames or other meth...

Страница 19: ...ighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners 5 Instructions for the final adj...

Страница 20: ...2 Integrated High Limit Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life...

Страница 21: ...p at highest unit in system If your units have automatic vents manual venting is unnecessary but it will speed up the proper filling of your system If your system is closed expansion tank system you m...

Страница 22: ...ly and turn clockwise to OFF Do not force WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance...

Страница 23: ...ostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 14 If flame needs adjusting do it as follow...

Страница 24: ...t shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reaches limit setting Gas valve should shut off and circulator running until th...

Страница 25: ...rioritized If I1 I2 is not used turn Economy Feature OFF House will not get or stay warm 1 Check for air bound radiators 2 Check thermostat settings including heat anticipator settings common on non d...

Страница 26: ...ol terminals and wire joints Rollout switch blown Have your service agent check heat exchanged for blockage Replace rollout switch with exact replacement Blocked vent blown Have your service agent che...

Страница 27: ...and piping should be checked at least once a season If vent piping shows any sign of leaking replace immediately WATER SYSTEM If system is to remain out of service during freezing weather always drain...

Страница 28: ...ter than calculated heat loss of the building Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements BOILERS FOR USE AT HIGH ALTITUDE Boiler is fa...

Страница 29: ...It will remain lit until the water temperature falls 10 The Fuel SmartHydroStat prevents burner operation while this LED is on See Differential explanation on page 6 of Hydrolevel Manual LWCO ACTIVE I...

Страница 30: ...position restore to correct position If this LED is blinking and the burner is not firing Make sure the plug connection or jumper on boilers where vent damper plug is not used is secure Make sure the...

Страница 31: ...ting a Check pilot flame Verify it is blue steady and envelops 3 8 to 1 2 in 10 to 13 mm of flame rod See Figure A 1 for possible flame problems and causes b If necessary adjust pilot flame by turning...

Страница 32: ...d position 4 Return thermostat to desired position 5 Place vent damper in open position to permit burner operation by using HOLD DAMPER OPEN switch located on damper controller 6 Thermostat controls b...

Страница 33: ...ross orange and yellow wires in Molex plug see Figure 4 This will create bypass of the damper boiler should then ignite If boiler ignites Go to section B 4 Vent Damper Troubleshooting Guide If boiler...

Страница 34: ...or heat 1 Thermostat not calling for heat 2 Burned out heat anticipator 3 Loose or broken connections 4 Off On operating limit pressure control or low water cut off 5 Off On blocked vent switch or fla...

Страница 35: ...35 Company Address Phone Company Name Tech Initials Service Performed Date PN 240013090 REV C 10 01 2021...

Страница 36: ...tion THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating l...

Отзывы: