ECR International Dunkirk WPSB 3 Series Скачать руководство пользователя страница 18

18

8 - GAS SUPPLY PIPING

CAUTION

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use 

any phone in your building.

• Immediately call your gas supplier from a 

neighbor’s phone.  Follow gas supplier’s 

instructions. 

• 

If you cannot reach your gas supplier, call the fire 

department.

!

!

  

CHECK GAS SUPPLY

Gas pipe to your boiler must be correct size for length of 

run and for total BTU per hour input of all gas utilization 

equipment connected to it. See Table 5 for proper size. 

Be sure your gas line complies with local codes and gas 

company requirements.

CONNECTING THE GAS PIPING 

See Figure 11.

Gas line enters boiler from right side.

• Use piping materials and joining methods acceptable 

to authority having jurisdiction.  In absence of such 

requirements:

• USA - National Fuel gas Code, ANSI Z223.1/NFPA 54
• Canada - Natural Gas and Propane Installation Code, 

CAN/CSA B149.1

•  Use pipe joint compound suitable for LP gas on male 

threads only.

•  Use ground joint unions.
•  Install sediment trap upstream of gas controls.
•  Use two pipe wrenches when making connection to gas 

valve to keep it from turning.

• 

Install manual shut-off valve in vertical pipe about 5 

feet above floor.

•  Tighten all joints securely.
•  Propane gas connections should only be made by 

licensed propane installer.

•  Two-stage regulation should be used by propane 

installer.

•  Propane gas piping should be checked out by propane 

installer.

CHECKING GAS PIPING

DANGER

Fire Hazard.  Do not use matches, candles, open 

flames, or other methods providing ignition source. 

Failure to comply will result in death or serious 

injury.

!

  

Pressure test boiler and gas connection before placing 

boiler in operation.

•  Pressure test over 1/2 psig (3.5 kPa).  Disconnect 

boiler and its individual gas shutoff valve from gas 

supply system.

•  Pressure test at 1/2 psig (3.5 kPa) or less.  Isolate 

boiler from gas supply system by closing manual gas 

shutoff valve.

•  Locate leakage using gas detector, noncorrosive 

detection fluid, or other leak detection method 

acceptable to authority having jurisdiction.  Do not 

use matches, candles, open flames, or other methods 

providing ignition source.

•  Correct leaks immediately and retest.

NATURAL GAS

Pipe Capacity - BTU Per Hour Input 

Includes Fittings

Length of 

Pipe - FT

½”

¾”

1”

1¼”

20

92,000

190,000

350,000

625,000

40

63,000

130,000

245,000

445,000

60

50,000

105,000

195,000

365,000

PROPANE GAS

Pipe Capacity - BTU Per Hour Input 

Includes Fittings

Length of 

Pipe - FT

Copper Tubing *

Iron Pipe

⅝”

¾”

½”

¾”

20

131,000

216,000

189,000

393,000

40

90,000

145,000

129,000

267,000

60

72,000

121,000

103,000

217,000

* Outside diameter

  Measure length of pipe or tubing from gas meter or 

propane second stage regulator.

Table 5 - Gas Pipe Sizes

Figure 11 - Gas Piping

PN 240013090 REV. C [10/01/2021]

Содержание Dunkirk WPSB 3 Series

Страница 1: ...3D WPSB 3DP WPSB 4D WPSB 4DP WPSB 5D WPSB 5DP WPSB 6D WPSB 6DP WPSB 7D WPSB 7DP WPSB 8D WPSB 8DP WPSB 9D WPSB 9DP Tested For 50 psi ASME Working Pressure Manufactured by ECR International Inc 2201 Dwy...

Страница 2: ...n this manual in effect at the time of printing of this manual ECR International Inc reserves the right to discontinue change specifications or system design at any time without notice and without inc...

Страница 3: ...7 Vent Damper Operation 17 8 Gas Supply Piping 18 9 Electrical Wiring 19 10 Wiring Diagram 20 11 General Instructions 21 12 Lighting Instructions 22 13 Operating Your Boiler 23 14 Service Hints 26 15...

Страница 4: ...Dimensions 1 1 4 RETURN PN 240013090 REV C 10 01 2021 Dimensions BOILER MODEL NUMBER DIMENSIONS INCH Boiler Volume Gallon FLUE DIAMETER A WIDTH WPSB 3 5 11 3 30 WPSB 4 6 14 4 60 WPSB 5 6 17 6 00 WPSB...

Страница 5: ...and all requirements before beginning installation FOR YOUR SAFETY READ BEFORE OPERATING Hot Water Can Scald Water heated to temperature for clothes washing dish washing and other sanitizing needs can...

Страница 6: ...be found on the NIOSH website https www cdc gov niosh topics silica NIOSH approved respirators manufacturers and phone numbers are also listed on this website Wear long sleeved loose fitting clothing...

Страница 7: ...ting and other performance criteria with the gas manifold and control assembly on the boiler per the latest revision of ANSI Z21 13 CGA 4 9 5 Install boiler such that gas ignition system components ar...

Страница 8: ...oric acid muriatic acid Cements adhesives and glues Photo processing plants Garages with workshops Furniture refinishing areas and establishments Laundry Chemicals Laundry detergents bleaches fabric s...

Страница 9: ...iping Size and arrange discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate Run pipe as short and straight as possible t...

Страница 10: ...herwise damage and or malfunction could be caused Recommended water quality is o Hardness Less than 150 mg L o Acidity level 7 8 pH o Sediments Particle size less than 50 micron If the water quality i...

Страница 11: ...damage to boiler and venting system Minimum design return water temperature to prevent condensation in boiler and venting is 120 F Minimum high limit setting is 140 F 1 Boiler used in heating system w...

Страница 12: ...12 Figure 5 Chilled Water Piping Figure 4 Typical Hot Water Piping 4 CONNECTING SUPPLY AND RETURN PIPING CIRCULATOR PUMP PN 240013090 REV C 10 01 2021...

Страница 13: ...Bypass Piping Circulator On Supply Figure 7 Bypass Piping Circulator On Return Bypass Piping Required For High Mass Large Water Content Systems 4 CONNECTING SUPPLY AND RETURN PIPING PN 240013090 REV C...

Страница 14: ...60 Volume 21 ft3 ACH x Total Input Mbh C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces All Outdoor Air Provide permanent opening s communicating directly or...

Страница 15: ...ent pipe should have any dips or sags Requirements 3 Boiler series is classified as a Category I Vent installation shall be in accordance with Venting of Equipment of the National Fuel Gas Code ANSI Z...

Страница 16: ...ances remaining connected to it At time of removal of existing boiler following steps shall be followed with each appliance remaining connected to the common venting system placed in operation while o...

Страница 17: ...ition Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed in open position to permit burner o...

Страница 18: ...regulation should be used by propane installer Propane gas piping should be checked out by propane installer CHECKING GAS PIPING DANGER Fire Hazard Do not use matches candles open flames or other meth...

Страница 19: ...ighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the burners 5 Instructions for the final adj...

Страница 20: ...2 Integrated High Limit Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life...

Страница 21: ...p at highest unit in system If your units have automatic vents manual venting is unnecessary but it will speed up the proper filling of your system If your system is closed expansion tank system you m...

Страница 22: ...ly and turn clockwise to OFF Do not force WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance...

Страница 23: ...ostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 14 If flame needs adjusting do it as follow...

Страница 24: ...t shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reaches limit setting Gas valve should shut off and circulator running until th...

Страница 25: ...rioritized If I1 I2 is not used turn Economy Feature OFF House will not get or stay warm 1 Check for air bound radiators 2 Check thermostat settings including heat anticipator settings common on non d...

Страница 26: ...ol terminals and wire joints Rollout switch blown Have your service agent check heat exchanged for blockage Replace rollout switch with exact replacement Blocked vent blown Have your service agent che...

Страница 27: ...and piping should be checked at least once a season If vent piping shows any sign of leaking replace immediately WATER SYSTEM If system is to remain out of service during freezing weather always drain...

Страница 28: ...ter than calculated heat loss of the building Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements BOILERS FOR USE AT HIGH ALTITUDE Boiler is fa...

Страница 29: ...It will remain lit until the water temperature falls 10 The Fuel SmartHydroStat prevents burner operation while this LED is on See Differential explanation on page 6 of Hydrolevel Manual LWCO ACTIVE I...

Страница 30: ...position restore to correct position If this LED is blinking and the burner is not firing Make sure the plug connection or jumper on boilers where vent damper plug is not used is secure Make sure the...

Страница 31: ...ting a Check pilot flame Verify it is blue steady and envelops 3 8 to 1 2 in 10 to 13 mm of flame rod See Figure A 1 for possible flame problems and causes b If necessary adjust pilot flame by turning...

Страница 32: ...d position 4 Return thermostat to desired position 5 Place vent damper in open position to permit burner operation by using HOLD DAMPER OPEN switch located on damper controller 6 Thermostat controls b...

Страница 33: ...ross orange and yellow wires in Molex plug see Figure 4 This will create bypass of the damper boiler should then ignite If boiler ignites Go to section B 4 Vent Damper Troubleshooting Guide If boiler...

Страница 34: ...or heat 1 Thermostat not calling for heat 2 Burned out heat anticipator 3 Loose or broken connections 4 Off On operating limit pressure control or low water cut off 5 Off On blocked vent switch or fla...

Страница 35: ...35 Company Address Phone Company Name Tech Initials Service Performed Date PN 240013090 REV C 10 01 2021...

Страница 36: ...tion THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating l...

Отзывы: