8
EDEM
SPLIT-TYPE ROOM AIR CONDITIONER
CONNECT THE CABLE TO THE INDOOR UNIT
electrical Work
connect the caBle to the indoor unit
Electric safety regulations for the initial Installation
If there is serious safety problem about the power supply, the
technicians should refuse to install the air conditioner and
explain to the client until the problem is solved.
Power voltage should be in the range of 90%~110%of rated
voltage.
The surge protector and main power switch with a 1.5 times
capacity of Max. Current of the unit should be installed in power
circuit. Ensure the air conditioner is grounded well.
The appliance shall be installed in accordance with national
wiring regulations. Do not operate your air conditioner in a wet
room such as a bathroom or laundry room.
An all-pole disconnection device which has at least 3mm
clearances in all poles, and have a leakage current that may
exceed 10mA, the residual current device(RCD) having a
rated residual operating current not exceeding 30mA, and
disconnection must be incorporated in the fixed wiring in
accordance with the wiring rules.
For the unit adopts auxiliary electric heater, keep at least 1
meter away from the nearest combustible materials.
According to the attached Electrical Connection Diagram
located on the panel of the indoor & outdoor unit to connect
the wire.
All wiring must comply with local and national electrical codes
and be installed by qualified and skilled electricians.
An individual branch circuit and single receptacle used only for
this air conditioner must be available. See the following table
for suggested wire sizes and fuse specifications:
1
1
2
2
3
3
4
4
5
5
6
6
7
8
9
NOTE
NOTE
The wire size of power supply cord and interconnected wire and
the current of the fuse or switch are determined by the maximum
current indicated on the nameplate which located on the side
panel of the unit. Please refer to the nameplate before selecting the
wire size, fuse or switch.
The controller of the air conditioner designed with a fuse protection
function under abnormal conditions, the specifications of the
fuse have printed on the circuit board, such as: 3.15A/250VAC,
T5A/250VAC, etc.
Before performing any electrical work, turn off the main power to
the system.
The inside and outside connecting cable can be connected without
removing the front grille.
The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor
power cord and interconnected cord type is H07RN-F.
Lift the indoor unit panel up, remove the electrical box cover by
loosening the screw.
Ensure the colour of wires of outdoor unit and the terminal Nos. are
the same to the indoor s respectively.
Wrap those cables not connected with terminals with insulation
tapes, so that they will not touch any electrical components. Secure
the cable onto the control board with the cord clamp.