61
5.5.3
Non- Functional Solenoid Valves-
A solenoid valve utilizes a control signal to activate a valve. Once the single control signal is
present on the coil of the solenoid, the valve should respond. To verify if a solenoid has power
you will need to understand that when power is applied most solenoids will hum (noise), vibrate
or get hot. You can verify that the control signal is being sent to the solenoid, and if it is and
the solenoid does not respond, turn the power OFF, and then with the use of your DVM in the
continuity mode, you will see some resistance in the solenoids coil (normally between 500 and
2000 ohms). If power is present then verify it gets water pressure from its source tube, if not
verify the in line strainer is not clogged. If you have good water flow but not through the
solenoid, then most likely the solenoid is clogged. Clean or replace it.
5.5.4
Stuck Solenoid Valve-
If you are getting a control voltage to the coil and the valve appears to not open, then this could
signal a clog of debris in the valve itself. You will need to open the valve and clean it or
replace it to fix the problem. If a solenoid valve continues to clog, you may want to consider
the use of a strainer up stream (pressure source) from the valve to stop debris from entering the
valve itself. If you find a strainer on the up stream side, make sure that the strainer is cleaned as
appropriate to make sure the system is functional.
In most cases the lack of response to the solenoid reflects a defective coil or valve. Replace the
defective solenoid valve. When ordering a replacement valve you must specify the valve size,
and actuator type and voltage.
Содержание CHC Series
Страница 1: ...Basics of Service and Troubleshooting ...
Страница 36: ...36 ...
Страница 37: ...37 ...
Страница 76: ...76 Soft Scale that is granular but hard from basin Soft Scale from tubes that is very granular ...
Страница 77: ...77 Hard Scale from tubes that is hard like Glass ...
Страница 82: ...82 6 2 Conductivity Controllers Walchem and LMI ...
Страница 83: ...83 ...
Страница 84: ...84 ...
Страница 101: ...101 6 10 Water Sampling Instructions ...
Страница 111: ...111 ...
Страница 120: ...120 ...
Страница 121: ...121 Eco Water CHC ...
Страница 122: ...122 6 15 Electrical Schematics EcoWater CHC ...
Страница 123: ...123 CHC EcoWater CHC CHC CHC ...
Страница 124: ...124 EcoWater CHC ...
Страница 125: ...125 EcoWater CHC ...
Страница 126: ...126 EcoWater C HC ...
Страница 127: ...127 CHC ...
Страница 128: ...128 ...