SISTEMS TYPE “E1” AND “E”
system diagram
System type “E1” comprises only one extinguishing detector,
one monitoring detector, and one nozzle. It is used for “small”
ducts up to 500mm diameter.
System type “E” comprises 2 extinguishing detectors,
2 monitoring detectors and 2 spray nozzles.
It is used for “large” ducts with over 500mm diameter.
Component list:
Type “E1” Type “E”
n. 2
n. 4
RIV - 601P/S Spark detector
n. 2
n. 4
SAM - 871
Mounting frame
n. 1
n. 1
PAN - 705M Control panel
n. 1
n. 1
SNA - 808L Alarm sounder beacon
n. 1
n. 1
EVS - 811
Solenoid valve
n. 1
n. 1
PAC - 846
Flow switch
n. 1
n. 2
UGN - 820
Spray nozzle
n. 1
n. 1 CON - 844
Pulse counter
n. 1
n. 1 SER - 851
Duct valve
CON and SER are options to be added to standard “E1”
and “E” systems.
DETECTION
EXTINGUISHING
MONITORING
See page MASP 13
for minimum distance between
detection and extinguishing
stop fan stop
alarm sounder beacon
SNA-808L
pulse counter
CON-844
power in
24Vdc
water in 3-4 bar
3/4" pipe
flow switch
PAC-846
duct valve
SER-851
spray
nozzle
UGN-820
spark
detector
RIV-601P/S
spark
detector
RIV-601P/S
mounting
frame
SAM-871
air in
mounting
frame
SAM-871
mounting
frame
SAM-871
spark
detector
RIV-601P/S
mounting
frame
SAM-871
spark
detector
RIV-601P/S
solenoid valve
EVS-811
control panel
PAN-705M
standard distance