DESP 23-GB
rev. 3 MAR17
EXTERNAL TEST LAMP UNIT
LAM-612P
Description
Designed to test the RIV-601P/S spark detector window integrity
against dust and dirt build-up.
Its use is recommended when internal test cannot be reliable
because of window being covered or darkened.
Its mounted like a spark detector, using the same SAM-871
mounting unit, over the duct in the opposite position, so as it will
be in front of the spark detector.
The LAM-612P unit includes an incandescent bulb whose light is
made pulsing by a modulator circuit at a particular frequency
which is recognised by the spark detector.
On the LAM-612P terminal block wiring is on the same
-
and
T+
terminals (5-6) as on RIV-601P/S spark detector.
Specifications
Cast aluminium case with IP66 protection (dust and water spray).
Power voltage 24Vdc ± 15% 50mA (TEST pulse: a short pulse
simulates a spark).
Electrical wiring on terminal block. Only
-
and
T+
terminals are
used (positions 5-6).
Weight 700g.
Model complying with 94/9 Atex directive suitable for application
on zone 22
II
3D Ex tD A22 IP66 T85°C.
LAM-612P
EXTERNAL TEST LAMP
4 mounting through holes
(which don’t have any
contact with the inside
space)
for M4x25 (minimum length) screws
140
39
180
85
65
Cable fitting M25
70
125
II
3D T85°C
Notes:
In order to ensure an
IP66 protection grade
the cover must be tightly closed turning the four screws provided.
The suggested closing torque value is 1 ÷ 1.5Nm.