rev. 3 MAR17
DESP 24-GB
EXTERNAL TEST LAMP UNIT
LAM-612P
OPERATING INSTRUCTIONS
The LAM-612P unit is operated when the Test key on the
control panel is depressed.
The control panel must be independent from the spark
detector system control panel.
This is very important in order that both the external and the
normal internal test can be performed.
In fact, if the external test gets no response by spark detector,
the internal test allows to verify if the detector is healthy, and
then the optical window is dirty, or if it is faulty, and a check is
needed.
When in operation, the LAM-612P unit delivers a 90° wide and
modulated light beam, which can excite a RIV-601P/S spark
detector at a 2m distance (provided all windows are clean).
ELECTRICAL WIRING
It is highly recommended to connect the enclosure base to a
good ground line using the
ground
terminal provided
inside up on the left. Then, connect base and cover using the
ground terminal provided inside the base lower on the right
and the ground terminal provided inside the cover lower on
the left.
All the ground terminals are signalled by ground label.
The ground connection must be done using a yellow-green
conductor and a M4 double crimp eyelet.
The yellow-green ground conductor must be longer than the
other conductors.
LAM-612P
+ L R C - T+ S
+24V
Control panel
TEST
other LAM-612P
units in parallel
Ground
bulb
T
-
mod
coll NPN
Ground
The
“S”
terminal must be left open
Note:
The LAM-612P unit can be also used to test the
IR flame
detector RIV-601P/F.
For
manual
test application the
S
terminal must be left open.
For
automatic
test application, the
T+
terminal must be
connected to +24V and the
S
terminal must be connected to
the S terminal of flame detector RIV-601P/F (in this case also
the ( - ) terminal of LAM-612P must be connected to the ( - )
terminal of RIV-601P/F.
With this connection the flame detector will react by generating
a short 0.5 sec. pulse every 4 sec. and will allow the alarm
panel to recognise the stand by state (short pulses) from the
fire alarm state (permanent on).
Application with one RIV-601P/S spark detector.
(SAM = SAM-871 mounting unit)
Application with two RIV-601P/S spark detectors.
Note:
the two spark detectors must be mounted in
opposite position.