11
WATER SPECIALIST DISC VALVE PROGRAMMING AND SERVICE MANUAL
ENG
8. OEM SYSTEM SETUP
STEP 1S
STEP 1S
– From normal mode, press DOWN and NEXT
simultaneously for about 3 seconds and release
STEP 2S
STEP 2S
– System Type – Use UP or DOWN to select
System Type.
SOFT – only softening related settings are viewed
FLT1 – only fi lter settings for BACKWASH and RINSE are
viewed
FLT2 – only fi lter regeneration related settings are viewed
Press NEXT to go to Step 3S. Press REGEN to exit OEM
System Setup.
STEP 1S
STEP 2S
STEP 3S
STEP 4S
STEP 5S
STEP 6S
STEP 7S
STEP 8S
STEP 9S
STEP 10S
STEP 11S
RETURN TO
NORMAL
MODE
STEP 3S
STEP 3S
– Regeneration Type - Use UP or DOWN to
select Regeneration Type.
RES – Delayed regeneration with variable reserve, at the
time of day set in Step 4I
DELY – Delayed regeneration at the time of day set in
Step 4I
On 0 – Immediate regeneration when Capacity Remaining
reaches zero
RES is only available when Step 2S is set to SOFT.
Press NEXT to go to Step 4S. Press REGEN to return to
previous step.
STEP 1S
STEP 2S
STEP 3S
STEP 4S
STEP 5S
STEP 6S
STEP 7S
STEP 8S
STEP 9S
STEP 10S
STEP 11S
RETURN TO
NORMAL
MODE
STEP 4S
STEP 4S
– Ionic Capacity - Use UP or DOWN to select
Ionic Capacity
(kg of CaCO
2
).
This display
appears if Step
3S is set to RES.
If DELY or ON 0 is selected in Step 3S, Volume Capacity
can be set, from 0.02 m
3
- 5700 m
3
or OFF. Press NEXT to
go to Step 5S. Press REGEN to return to previous step.
STEP 1S
STEP 2S
STEP 3S
STEP 4S
STEP 5S
STEP 6S
STEP 7S
STEP 8S
STEP 9S
STEP 10S
STEP 11S
RETURN TO
NORMAL
MODE
STEP 5S
STEP 5S
– Fill Type - Use UP or DOWN to select POST
or PRE. This display only appears if Step 2S is set to
SOFT. Press NEXT to go to Step 6S. Press REGEN to
return to previous step.
STEP 1S
STEP 2S
STEP 3S
STEP 4S
STEP 5S
STEP 6S
STEP 7S
STEP 8S
STEP 9S
STEP 10S
STEP 11S
RETURN TO
NORMAL
MODE
STEP 6S
STEP 6S
– Regenerant Draw Type - Use UP or DOWN
to select DN or UP regenerant draw. This display only
appears if Step 2S is set to SOFT. Press NEXT to go to
Step 7S. Press REGEN to return to previous step.
NOTE: The following displays show the settings when set
to SOFT, POST and DN. When set to FLT1, FLT2, PRE or
UP, the order and number of cycles will differ.
STEP 1S
STEP 2S
STEP 3S
STEP 4S
STEP 5S
STEP 6S
STEP 7S
STEP 8S
STEP 9S
STEP 10S
STEP 11S
RETURN TO
NORMAL
MODE
STEP 1S
STEP 2S
STEP 3S
STEP 4S
STEP 5S
STEP 6S
STEP 7S
STEP 8S
STEP 9S
STEP 10S
STEP 11S
RETURN TO
NORMAL
MODE