The thermostat communicates with the wireless damper 
installed in the duct leading to the space.  The thermostat 
monitors the space temperature, the setpoint temperature and 
System Mode setting. 

For most applications, set the System Mode to Off and the 
Thermostat Mode to Hold. When the room is in use, set the 
System Mode to Heat or Cool to correspond to the HVAC 
equipment setting. Adjust the setpoint temperature to 
automatically adjust the airflow to achieve the desired space 
temperature. When the room is unoccupied, change the 
System Mode back to Off so the energy saving Off Airflow 
Level is used.

Off Operation

The thermostat sets the Airflow to the Off Airflow Level 
selected in the Installer options.

Heat Operation

If the setpoint temperature is higher than the space 
temperature, the thermostat makes periodic adjustments to the 
damper to increase the airflow to provide more heating to the 
space. If the setpoint temperature is lower than the space 
temperature, the thermostat makes periodic adjustments to the 
airflow to provide less heating airflow to the space.

Cooling Operation

If the setpoint temperature is lower than the space 
temperature, the thermostat makes periodic adjustments to 
increase the airflow to provide more cooling to the space. If the 
setpoint temperature is higher than the space temperature, the 
thermostat makes periodic adjustments to the airflow to 
provide less cooling airflow to the space.

1

Operation

USER

1

Select System Mode

Inside

Mo

Schedule

Day

AM

Set To

MENU

MODE

NEXT

ENTER

SYSTEM

OFF

There are 3 system modes - Off, Heat or Cool. The System 
Mode selected by the user needs to correspond to the current 
system mode of the HVAC equipment. 

OFF MODE

In Off Mode, the thermostat sets the airflow to the Off Airflow 
Level set by the installer - Installer Option 10.

Press the 

 key to 

display Off, Heat or Cool.

SYSTEM

i

HEAT MODE

Ensure that the HVAC equipment is in Heating before 
setting the system mode to Heat. Not doing so will cause 
the thermostat to improperly adjust the damper and will 
result in discomfort in the space.

i

COOL MODE

Ensure that the HVAC equipment is in Cooling before 
setting the system mode to Cool. Not doing so will cause 
the thermostat to improperly adjust the damper and will 
result in discomfort in the space.

1

Select Thermostat Mode 

HOLD MODE

Press the 

 key to display 

Hold 

or

 Schedule.

MODE

Inside

Mo

Hold

AM

Set To

MENU

MODE

NEXT

ENTER

SYSTEM

HEAT

There are 2 Thermostat Modes - Hold and Schedule. Hold 
mode is used in most applications. The Schedule mode may 
be used for commercial applications.

In Hold mode the thermostat adjusts the airflow based on the 
setpoint temperature set by the user and System Mode 
selected, Heat or Cool.

SCHEDULE MODE

In Schedule mode the thermostat uses the factory or user set 
schedule(s) to adjust the airflow at a specific time to the 
Nighttime Airflow Level set by the installer - Installer Option 9. 
The System Mode, Heat or Cool, should correspond to the 
HVAC equipment system setting.

1

Overriding the Night or Off Operation

To adjust the temperature during 
Nighttime operation, press the 

UP

 

or 

DOWN

 key. After 2 hours, the 

thermostat returns to Nighttime 
operation.

Inside

Mo

Schedule

PM

Set To

MENU

MODE

NEXT

ENTER

SYSTEM

HEAT

Night

Ensure that the system mode 
selected corresponds to the 
HVAC equipment setting.

i

2

Содержание T200WLD

Страница 1: ...low to the space The thermostat maintains the temperature using the system mode and setpoint temperature set by the user and the space temperature Automatically controls airflow based on selected syst...

Страница 2: ...Off Heat or Cool The System Mode selected by the user needs to correspond to the current system mode of the HVAC equipment OFF MODE In Off Mode the thermostat sets the airflow to the Off Airflow Leve...

Страница 3: ...d NEXT Schedule PM MENU MODE NEXT ENTER SYSTEM Night All days are displayed The number in the upper right corner shows the day of the week being selected or deselected 1 is Monday 2 is Tuesday etc Pre...

Страница 4: ...ange is reduced Batteries should be replaced with AA alkaline or lithium batteries Inside Mo Schedule AM Set To MENU MODE NEXT ENTER SYSTEM HEAT Day Inside Mo Schedule AM Set To MENU MODE NEXT ENTER S...

Страница 5: ...Range Range Range Range 1 to 8 1 to 8 1 to 5 F o 60 to 90 F o 55 to 80 F o 0 to 100 0 to 100 0 8 F 1 16 F 5 to 30 minutes 0 On with key Default 1 1 1 F o 80 F o 65 F o 50 50 0 8 F 10 minutes On with k...

Страница 6: ...thermostat makes an adjustment to the airflow If the deadband is set for 1 degree the room temperature must be more than 1 degree warmer or cooler than the setpoint temperature before the damper posit...

Страница 7: ...ss 1 The dampers are powered by 24VAC and require only 2 8VA when operating and only 1VA when holding A 40VA transformer can power up to 10 dampers The damper or dampers controlling airflow to the spa...

Страница 8: ...ise position the damper will completely close In the fully clockwise position the damper will close to about 50 closed allowing some air to pass even when the user sets the damper to fully closed Repl...

Отзывы: