If only one wireless thermostat is used in the installation, the 
default Zone 01 and Home Address 01 can be used.  Skip to 
Option 03. If multiple wireless thermostats are used, each 
thermostat and damper have to be programmed with a unique 
Zone number.  The first thermostat can use the factory set 
Zone 01 and Home Address 01.

Press the 

 keys to 

set the Zone number for the 
thermostat from Zone 1 to 8.

Press the 

NEXT

 key to go to 

the next option. Or, press the

 

ENTER

 key to save and exit

UP/DOWN

Option

Zone

CANCEL

NEXT

ENTER

02  Changing the Home Address Number

01  Changing Zone Number

SYSTEM

The Home address is used when two or more installations are 
within 300’ of one another. This allows neighbors, different 
departments or floors to use the wireless thermostats and not 
interfere with each other.  Skip to Option 04 if no other user 
groups are nearby.

Option

Home

CANCEL

NEXT

ENTER

Press the 

 keys to 

set the Home Address 
number for the thermostat 
from Home 1 to 8. If multiple 
departments are installing 
wireless thermostats, each 
department should use a

UP/DOWN

SYSTEM

different Home number to insure the Damper in another 
department is not inadvertently changed.

Press the 

NEXT

 key to go to the next option. Or, press the 

ENTER

 key to save and exit the installer options, or press the

 

CANCEL

 key to exit installer options without saving.

the installer options, or press the

 key to exit installer 

options without saving.

 CANCEL

The difference between the setpoint and room temperature 
must exceed the deadband temperature before the thermostat 
makes an adjustment to the airflow. If the deadband is set for 1 
degree, the room temperature must be more than 1 degree 
warmer or cooler than the setpoint temperature before the 
damper position is changed

03  Setting Deadband Temperature

Option

CANCEL

NEXT

ENTER

SYSTEM

Press the 

 keys to 

set the Deadband 
Temperature. Range is 1 to 5 
degrees. 

Press the

 NEXT 

key to go to 

the next option. Or, press the

 

ENTER

 key to save and exit

UP/DOWN

the installer options, or press the

 key to exit installer 

options without saving.

 CANCEL

The Update Time Interval 
determines how often the 
thermostat sends data to the 
wireless damper actuator.  
Shorter times will use more 
battery life and provide faster 
response to temperature

04  Set Update Time Interval

Option

CANCEL

NEXT

ENTER

SYSTEM

changes.  The default setting of 10 minutes is a good 
compromise in battery life and responsiveness.

Press the 

 keys to set the Update Time from 5 to 30 

minutes. 

Press the 

NEXT

 key to go to the next option. Or, press the

 

ENTER

 key to save and exit installer options, or press the

 

CANCEL 

key to exit installer options without saving.

UP/DOWN

Access installer options by pressing and holding the unmarked 
key below the System key for seven seconds. The LCD will 
display Option 01 for setting the Zone number.

Press or hold the 

NEXT

 key to advance to the next option.  

The LCD will advance to Option 10 and return to Option 01.  
Press the 

CANCEL

 key to exit the option selections.  Press the

 

ENTER

 key to save all options.

Press and hold the 
unmarked key for seven 
seconds to access the 
installer options.

Option 01 will be displayed.

Accessing Installer Options

Inside

Mo

Schedule

Day

AM

AUTO

Set To

MENU

HOLD

NEXT

ENTER

SYSTEM

Option

Zone

CANCEL

NEXT

ENTER

6

Содержание T200WLD

Страница 1: ...low to the space The thermostat maintains the temperature using the system mode and setpoint temperature set by the user and the space temperature Automatically controls airflow based on selected syst...

Страница 2: ...Off Heat or Cool The System Mode selected by the user needs to correspond to the current system mode of the HVAC equipment OFF MODE In Off Mode the thermostat sets the airflow to the Off Airflow Leve...

Страница 3: ...d NEXT Schedule PM MENU MODE NEXT ENTER SYSTEM Night All days are displayed The number in the upper right corner shows the day of the week being selected or deselected 1 is Monday 2 is Tuesday etc Pre...

Страница 4: ...ange is reduced Batteries should be replaced with AA alkaline or lithium batteries Inside Mo Schedule AM Set To MENU MODE NEXT ENTER SYSTEM HEAT Day Inside Mo Schedule AM Set To MENU MODE NEXT ENTER S...

Страница 5: ...Range Range Range Range 1 to 8 1 to 8 1 to 5 F o 60 to 90 F o 55 to 80 F o 0 to 100 0 to 100 0 8 F 1 16 F 5 to 30 minutes 0 On with key Default 1 1 1 F o 80 F o 65 F o 50 50 0 8 F 10 minutes On with k...

Страница 6: ...thermostat makes an adjustment to the airflow If the deadband is set for 1 degree the room temperature must be more than 1 degree warmer or cooler than the setpoint temperature before the damper posit...

Страница 7: ...ss 1 The dampers are powered by 24VAC and require only 2 8VA when operating and only 1VA when holding A 40VA transformer can power up to 10 dampers The damper or dampers controlling airflow to the spa...

Страница 8: ...ise position the damper will completely close In the fully clockwise position the damper will close to about 50 closed allowing some air to pass even when the user sets the damper to fully closed Repl...

Отзывы: