background image

 

 

24 

 

   

Installation, Operation, And Service Instructions

 

 

 
 

 
 
 

FILL SYSTEM

  

 

1.

 

Close manual air vents (if used) and automatic air vents.  Attach hose to boiler drain 
on return connection and run to a drain or to outdoors.  Open drain cock and close 
shutoff valve on boiler supply pipe. 

2.

 

HEATING ONLY – SINGLE ZONE SYSTEM--- 
Open manual valve in cold water feed line and set the fill valve to fast fill.  Allow 
water to flow through the system and out the hose until there is a steady flow of water 
through the hose with no air bubbles.   
Next, open the shutoff valve in the drain until air bubbles cease.   Then take the fill 
valve off fast fill, close the drain cock, remove the hose and open all automatic air 
vents.   
Also open all manual air vents one at a time and close when water squirts out.  
Observe the temperature/pressure gauge.  System pressure with a cold fill should be 
in the 12 to 14 psi range. 

3.

 

MULTI-ZONE SYSTEMS-HEATING ONLY OR HEAT & DOMESTIC HOT 
WATER WITH ZONE VALVES--- 
To ensure good circulation through all zones with no air pockets, each zone should be 
purged of air individually.  With all zone valves in the manual open position let water 
flow through the system by opening the drain cocks so water can exit the system 
through a hose as in 1. above. 
When system seems to be full and free of air, close the drain cock, and the shutoff 
valve on the boiler supply pipe, leaving the manual valve on the cold water feed open.  
Now release the manual openers to close all but one zone valve.  Open the drain cock 
and put the fill valve on fast fill.  When the flow through hose becomes steady with 
no air bubbles, take the fill valve off fast fill and then close the drain cock. 
Repeat this procedure with each zone until all zones have been purged.  Open the 
shutoff valve on the boiler supply pipe.  Then open all manual air vents one at a time.  
When water sprays out of the air vents should have the cap loosened so it can vent air. 

4.

 

MULTI-ZONE SYSTEMS ZONED WITH CIRCULATORS--- 
Following the same procedures as in 3. above using the manual shutoff valves to 
isolate a zone instead of zone valves. 

5.

 

Check system pressure on the temperature/pressure gauge on the boiler.  Pressure 
should be in the 12 to 14 psi range.  If pressure is over 14 psi drain a little water out 
with the drain cock.  Watch gauge for a few minutes to ensure pressure does not build 
back up.  If pressure is too high with system cold there is a good possibility the relief 
valve will blow off when the system is brought up to temperature.  Too high a 
pressure with the system cold indicates a faulty fill valve. 

 
 
 

BOILER START-UP AND ADJUSTMENTS 

Содержание OWB-15

Страница 1: ...with proper filtration to the inside supply tank is acceptable 6 The fuel pump included with burner is to be mounted at tank level or below PUMP MUST BE MOUNTED HORIZONTAL AND LOCATED NEXT TO WASTE O...

Страница 2: ...ked in the wirebound crate Install in tappings provided at the top rear of the boiler as shown in Figure 13 Figure 13 b Take the boiler drain from the same carton and connect it to the 3 4 inch openin...

Страница 3: ...he 2 x 1 1 4 inch bushing which is supplied in the boiler supply and return ports and must provide his own boiler drain and circulating pump 1 Accessories for Boilers OWB 35 and OWB 50 Figure 14 Suppl...

Страница 4: ...em is to comply with ASME code 1 Backflow Preventer Required by many State and local codes 3 Additional circulating pumps or zone valves may also be required if the system is to be multi zone or if it...

Страница 5: ...e pressure reducing fill valve may be piped with 1 2 inch pipe Figure 17 Closed Type Expansion Tank Supply to System Shutoff Valve Fill Valve Cold Water Feed Return From System Circulation Pump Drain...

Страница 6: ...piped to a drain or must terminate 6 above floor to eliminate damage to the structure or personal injury It must not be piped to a point where freezing might occur 1 MULTIPLE ZOINING WITH ZONE VALVES...

Страница 7: ...drop below about 135 Degree F for an extended period of time Return water temperatures of 130 Degree F or lower will cause condensation on the exterior surface of the heat exchanger and corrosion and...

Страница 8: ...systems that employ outdoor reset control present a potential problem with low return water temperatures and condensation The boiler must be protected from condensation in such cases by using a by pa...

Страница 9: ...r output is available to recover the storage tank quickly and should be used where supply of domestic hot water on demand is critical For this application use a full throated valve with a minimum pres...

Страница 10: ...t for heating Because the tank is usually close to the boiler the pressure drop through the coil circuit will generally be less than through a heating zone circuit which will provide some measure of p...

Страница 11: ...gravity circulation Install a balancing valve in each zone and adjust so that flow in each zone is about the same see Figure 24 While this basic system does not provide priority for domestic hot water...

Страница 12: ...iler shall be not less than 1 8 GPM for each 100 000 BTU HR of gross boiler output Size blend pump accordingly See Table 3 Blend Pump Primary Secondary Pump Boiler Model GPM GPM OWB 9 OWB 15 OWB 25 OW...

Страница 13: ...e 27 Blend Pump Check Valve System Supply System Circulator Pressure Reduction Valve Backflow Preventer From City Water Supply Expansion Tank System Return Amtrol 720 Air Eliminator or Equal To Size B...

Страница 14: ...REVERSE RETURN FLOW WITH BLEND PUMP Figure 28 Blend Pump Check Valve System Supply System Circulator Pressure Reduction Valve Backflow Preventer From City Water Supply Expansion Tank System Return Amt...

Страница 15: ...t fill in the space between the burner blast tube and the insulation block on the inside of the burner door with refractory mix provided Burner Mounting Figure 29 OWB 35 and OWB 50 Burner Mounting Boi...

Страница 16: ...on top of wraparound insulation This will provide double thick insulation on top of the boiler block 4 Remove flue collector clean out covers 62 5 Push the two smaller pieces of insulation 60 onto th...

Страница 17: ...WB 9 OWB 15 and OWB 25 Jacket Installation Instructions 1 Attach the rear jacket mounting brackets 7 to rear tie rod ends on back of boiler using the 12mm nut 9 provided on the end of each tie rod 2 A...

Страница 18: ...nel 5 using four 10x1 2 sheet metal screws 9 Attach the flue collector cover 4 using four 10x 1 2 sheet metal screws 10 Press the door switch 16 into the door switch bracket 17 Connect the door switch...

Страница 19: ...C2 on the L8148A are not used A DPST Honeywell RA832A may be substituted in place of the R845A using the X and X terminals in place of the 5 and 6 terminals on a R845A A call for heat from any thermos...

Страница 20: ...nnections so that any zone valve that opens will also start the circulator and fire the boiler assuming the high limit is not open Zone valve terminal TH TR has no internal connection on the zone valv...

Страница 21: ...ATER BLOCK Fuse Power Switch BLK BLK WHT WHT RED WHT WHT WHT RED BLU RED Power Plug Looking at Terminal Side BLK Oil Valve BLK GRN Power Socket Electrical Box Looking at Socket Side Burner Assembly Th...

Страница 22: ...K BLK WHT WHT RED WHT WHT WHT RED BLU RED Power Plug Looking at Terminal Side BLK Oil Valve BLK GRN Power Socket Electrical Box Looking at Socket Side Burner Assembly N H Oil Pump WHT BLK WHT YEL Serv...

Страница 23: ...23 Figure 35 WIRING DIAGRAM ZONE WIRING USING HONEYWELL V8043F VALVES FACTORY BOILER WIRING NOT SHOWN SEE FIGURE 33 OR 34 Figure 36 WIRING DIAGRAM CIRCULATOR ZONE WIRING USING HONEYWELL R845A S FACTO...

Страница 24: ...n exit the system through a hose as in 1 above When system seems to be full and free of air close the drain cock and the shutoff valve on the boiler supply pipe leaving the manual valve on the cold wa...

Страница 25: ...Oil Primary This will allow the burner to run during the pump priming process 9 Priming the oil pump Open bleeder valve one turn until all air is expelled Figure 4 This may need to be done twice to i...

Страница 26: ...ng connections to ensure there are no flue gas leaks Seal any leaks found with High Temperature Silicone Sealant 6 Check flue gas temperature at the test point in the breeching If gross flue gas tempe...

Страница 27: ...ion And Service Instructions 27 Figure 37 Electrode Adjusment Diagram Figure 38 Nozzle Assembly Detail When cleaning inspect all three pieces thoroughly When disassembling and reassembling nozzle keep...

Отзывы: