5.2
Start up
1.
Ensure that the metering line is not shut off at any place.
2.
Chapter 4.2.3 ‘Venting function’ on page 21
).
5.2.1
Setting back-pressure (pressure holding)
The back-pressure is adjusted to 0,1 MPa (1 bar) + 20%, on the manufacturing side.
If a different pressure is required, the adjustment can be done as follows:
1.
Remove the sealing plug (Pos. 10) at the pressure holding operation button (Pos. 2)
either manually or with a small screwdriver.
2.
Disengage the screw (Pos. 11) and remove the operation button.
3.
Pull out the adjustment button (item 12) slightly and set the desired counter pressure
by turning (right stop approx. 0,1 MPa (1 bar), left stop approx. 0,05 MPa (0,5 bar).
4.
Then fixate the adjustment button by pushing it back in, replace the operation button,
tighten the screw and insert the sealing plug.
Fig. 3: Setting back pressure (pressure holding function)
2
Operation button
10 Sealing plug
11 Screw
12 Adjustment button
Installation and Start-up
23
417101224 Rev. 05-05.2019