Installation and User Manual. Version V03.B03_EN (23/09/2015)
ecoGEO
81
ECOFOREST Geotermia
12. TECHNICAL SPECIFICATIONS
12.1. TECNICAL DATA
In the Table 12.1 you can find the main technical specifications of the heat pumps ecoGEO.B1, B2 y B3.
Geothermal heat pump ecoGEO B
TECHNICAL DATA
Unit
ecoGEO B1
ecoGEO B2
ecoGEO B3
3-12
5-22
3-12
5-22
3-12
5-22
Application
Heating and DHW
-
●
●
●
●
●
●
Active cooling
-
●
●
Built-in free cooling
-
●
●
Single-phase
Power supply
230 V / 50 Hz, 1/N/PE~
-
●
●
●
●
●
●
Magnetothermal protection
A
32
40
32
40
32
40
Three-phase
power supply
400 V / 50 Hz, 3/N/PE~
-
●
●
●
Magnetothermal protection
A
--
16
--
16
--
16
Refrigerant
Type
-
R410A R410A R410A R410A R410A R410A
Components
Compressor
-
Scroll with Copeland inverter
Expansion valve
-
Carel Electronics
Heat exchangers
-
Alfa Laval plates
Circulation pumps
-
Wilo High-efficiency variable speed (Class A)
Expansion vessels
-
Heating-cooling circuit and brine circuit
Eficiencia
Heating output
1
kW
3-15
5-26
3-15
5-26
3-15
5-26
Heating output
2
kW
3-14
5-23,5
3-14
5-23,5
3-14
5-23,5
Electric power consumption
2
kW
0,7-3,7
1,4-5,5
0,7-3,2
1,4-5,5
0,7-3,2
1,4-5,5
COP
2
-
4,6
4,9
4,6
4,9
4,6
4,9
EER
3
-
--
--
--
--
6,1-6,9
6,1-6,9
Cooling capacity
3
kW
--
--
--
--
4-16,3
6,9-30
Free cooling capacity
kW
--
--
6
6
--
--
Refrigerant
circuit
Refrigerant charge
kg
1,35
1,70
1,35
1,70
1,50
2,00
Masimum working pressure
bar
42
42
42
42
42
42
Compressor oil type
-
POE
POE
POE
POE
POE
POE
Compressor oil charge
kg
1,18
1,18
1,18
1,18
1,18
1,18
Heating-
cooling circuit
Maximum/minimun temperature
ºC
60/20
Maximum working pressuere
bar
3
Nominal flow rate
l/h
1200 - 4500
Brine circuit
Maximum/mínimum teperature
ºC
20/-10
Maximum working pressure
bar
3
Nominal flow rate
l/h
1200 - 4500
Recomended antifreeze
5
-
Propylene glicol / freezing point of wáter at -17 ±2 ºC
DHW
Maximun DHW temperature
ºC
55
55
55
55
55
55
Maximum legionella temperature
ºC
70
70
70
70
70
70
Soundproofing
Noise emission level
4
dB
42
42
42
42
42
42
Dimensions
Height x width x depth
mm
1000 x 600 x 700
Weight
Unladen weight (without
packaging)
kg
170
175
170
175
175
180
1)
Consultar siempre las regulaciones regionales antes de utilizar el medio anticongelante.
1)
According to EN 14511, 5/2
– 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
2)
According to EN 14511, 0/-3
– 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
3)
According to EN 14511, 7/12
– 30/35 ºC (including circulation pumps, inverter and with single-phase power supply).
4)
According to EN 14511. Values in parentheses include the compressor's acoustic isolation kit.
5)
Please, always check the regional regulations before using the antifreeze.
Table 12.1.
Tabla de características técnicas de las bombas de calor ecoGEO B1, B2 y B3.