1
8
EN
420010331102
M ulticalor 45 ÷ 140 AB/AB
Pull up the switch on the ter-
minal strip to keep burner in
first stage.
I
I
I
I
I
I
I
I
I
I
I
I
I
- Manual low flame position
II
-
Manual operation : high flame position
Automatic operation : HI-LOW flame position by
the HI-LOW thermostat.
DESCRIPTION OF CONTROL PANEL
1 - Fuse
2 - Termal lock-out lamp
3 - Light-oil working lamp
4 - Gas working lamp
5 - High-low flame switch
6 - Main switch I / O
7 - Gas/Light-oil selector switch:
1- Light-oil operation
2- Gas operation
8 - Lockout disable push button
0
I
1
2
6
3
5
4
8
0 1
2
7
0 1
2
0 1
2
0 1
2
0 1
2
ADJUSTING THE FIRING HEAD
The adjustment of the com-
bustion head position is car-
ried out in order to
obtain the best combustion
efficiency. When installed for
small output operations,
the head shall be adjusted back.
For maximum operation the position is fully forward.
Steps: loosen the locking screw of A lever. Move the lever to
the needed position. Tighten back the locking screw.
A
min.
m
a
x.
A
min.
m
a
x.
MULTICALOR
45-70-100
MULTICALOR
140
NOZZLE CLEANING AND REPLACEMENT
Use only the suitable box wrench provided for
this operation to remove the nozzle, taking
care to not damage the electrodes. Fit the new
nozzle with the same care.
Note:
Always check the position of electrodes
after having replaced the nozzle (see illustra-
tion). A wrong position could cause ignition
troubles.
5
÷
6 mm
3
÷
4 mm
2 fi
a
mme
I
0
REMOVING THE BLAST TUBE
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 µA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 µA.
LGB 22
QRA
AGQ1.1A27
1
2
SW
SW
BL
BL
FLAME DETECTOR SYSTEM CHECK
SW = BLACK
BL = BLU