Start up
Oil side
!
Risk of air blast!
Continuously check CO, CO2 and
soot emissions when adjusting the
output of the burner. Optimise
combustion values in the event of
CO formation. CO must not exceed
50 ppm.
Start up the burner
The control box starts the pre-purge cycle,
the fan motor and the oil motor and opens
the air flaps in full open positon.
At the end of pre-purging, the control box
drives the servomotors into the igniton
positon and starts the igniton transformer.
After a few seconds the control box opens
the oil valve and starts the flame. After the
flame stabilisaton the control box drives
the servomotor in the low flame.
In case of faulty igniton, the control box
switches the burner into safety condition,
in such a case you must rearm the burner.
Gradually increase burner output from the
low flame to the high flame and set oil
servomotor curve in order to have
a stable flame. Refer to LAMTEC manual
attacched.
Adjusting the maximum oil flow rate
Put the selector on the oil operation. Adjust
the oil pressure reading the value on the
return manometer / pressure gauge
according to the nozzle tables provided in
the appendix. Oil adjustment is accompli-
shed through LAMTEC parameters setting.
Refer to LAMTEC manual attacched.
NOTE:
the pump pressure is set from the
factory at the pressure required nozzle
pressure required as per table of nozzle
selection in appendix. If the output
required is different from the one set from
the factory the pressure can be adjusted
according to the instruction below.
Adjusting the maximum air flow rate
Air and Oil adjustment are accomplished
through LAMTEC parameters setting.
Refer to LAMTEC manual attacched.
Firing head setting
The firing head is pre-adjusted at the 50%
from the factory. The setting fully open
enables to reach the full power of the
burner and full close to reach the minimum
power of the burner. The optimal position
depends on the output that we need to
reach but the default setting shall be
modified only when you are not able to
reach the suggested combustion value by
adjusting the air flow in the maximum
flame.
Servomotor LAMTEC
Air adjustment is accomplished through
LAMTEC parameters setting. Refer to
LAMTEC manual attacched.
Select the oil operation in order to proceed with start up on the oil side. On the selector put the operation on minimum capacity.
KMV
KMP
!
KMP KMV contactor:
check the oil pump motor and air fan motor
rotation and keep KMP pressed till the oil circuit is loaded.
If the rotation if not correct invert the two phases on the power supply.
0=STOP
2=GAS
1=OIL
A
MIN
MAX
A
420010915000
EN
www.ecoflamburners.com