www.ecoflamburners.com
EN
420010372804
Start up
Adjusting burner output
Presetting diagrams in appendix
Before start-up adjust the burner
parameters according to the settings given
in the diagrams for GAS/LPG.
These values have been determined in
our test labs and are useful for the first
switch-on as final setting must be done
using a combustion analyzer.
How to read and adjust the values:
- determine the output required
- determine the combustion chamber back-
pressure
- read the position of the head in the
diagram and adjust it according.
- read the position of the air flap and adjust
it according.
pressure in the combustion chamber (mbar)
output (kW)
head gas pressure (on elbow) (mbar)
head position
air damper position
+
-
A
+
-
+
-
B
+
-
A
+
-
+
-
B
MAX GAS 40 P
MAX GAS 70-120 P
MAX GAS 40 P
MAX GAS 70-120 P
Air damper setting (A).
To act on the screw in figure:
• to increase output,
turn screwdriver clockwise
• to reduce output,
turn screwdriver counterclockwise
Firing head setting (B).
To act on the screw in fi gure:
• turn Allen key till you reach the
requested value (index 0-4,5).
Optimising combustion values
The factory setting shall be modified
according to the output requeired.
N.B.
observe the minimum required
flue gas temperature specified by
the boiler manufacturer and the
requirements demanded of ue gas ducts
for avoiding condensation.
Warning
:
Recording of initial
commissioning data is recom
mended.
WARNING
Risk of air blast!
Continuously check CO, CO2 and
soot emissions when adjusting the
output of the burner. Optimise combustion
values in the event of CO formation. CO
must not exceed 50 ppm.
DANGER
Adjustment of gas solenoid valve
Refer to the gas train manual for
the gas setting of the gas train
selected.
Содержание MAX GAS 120 P
Страница 54: ...54 www ecoflam burners com 420010372804 RU 1 2 3 2 3 5 A B A B 1 WARNING 30 C 5 1 2 3 WARNING DANGER...
Страница 55: ...55 www ecoflam burners com 420010372804 RU 1 2 3 4 E BCU WARNING DANGER WARNING...
Страница 65: ...65 www ecoflam burners com 420010372804 EN IT FR ES RU...
Страница 66: ...66 www ecoflam burners com 420010372804 EN IT FR ES RU...
Страница 67: ...67 www ecoflam burners com 420010372804 EN IT FR ES RU...