15
www.ecoflamburners.com
EN
420010372804
Symbol fault
Fault
Cause
Remedy
No heat request
Thermostats defective or
incorrectly adjusted
Adjust the thermostats, replace if
necessary.
Sullply voltage lower than minimum
allowed value
Drop in supply voltage or
power failure.
Control unit malfunction
Check the cause of the fall in voltage or the
power failure
Replace the control unit.
Burner starts briefl y when switched on,
switches off and the red LED lights up
Control unit was
deliberately shut down
Unlock the unit
Burner does not start
Air pressure switch: not in rest position
Incorrect adjustment
Contact is welded
Readjust the pressure switch
Replace the pressure switch
Burner does not start
Low gas pressure
Insufficient gas pressure
Gas pressostat wrongly set or defective
Check gas lines
Clean the filter
Check the gas pressostat or replace the
compact gas unit
Burner blower starts up
Burner does not start
Air pressure switch: the contact does
not close
Check the pressure transmitter (foreign
bodies) and wiring
Burner blower starts up
Burner does not start
Flaring during pre-ventilation or pre-
ignition
Check the valve
Check fl ame monitoring
The burner starts, the ignition
switches on, then failure
No flame at the end of the safety period
Gas throughput set incorrectly
Faulty fl ame monitoring circuit
No ignition arc
Electrode(s) short-circuited
Ignition cable damaged or defective
Ignition transformer defective
Automatic combustion control unit
Solenoid valves do not open
Valves jamming
Adjust the gas throughput
Check the condition and position of the
ionisation sensor in relation to earth
Check the condition and connections of the
ionisation ci rcuit (cable(s) and
measurement bridges)
Adjust, clean or replace electrode(s)
Connect or replace the cable(s)
Replace the transformer
Replace the control unit
Check the cabling between the control
unit and external components
Replace the compact gas unit
Replace the valves
Flame extinguishing
during operation
Air pressure switch: contact opens
during startup or during operation
Flame failure during operation
Adjust or replace the pressure switch
Check the ionisation sensor circuit
Check or replace the automatic
combustion control unit
Service
Troubleshooting
Fault diagnosis and repair
In the event of a malfunction, first check
that the prerequisites for correct
operation are fu llfilled:
1. Is the system connected to the
power supply?
2. Is there any gas pressure?
3. Is the gas shut-off valve open?
4. Are all control and safety devices,
such as the boiler thermostat, low water
level detector, limit switch, etc. adjusted
correctly?
If the malfunction persists, use the
following table. It is not permitted to repair
any components relevant to safety.
These components must be
replaced by parts with the same
order number.
Only use original spare parts.
In the event the burner stops, in
order to preventany damage to
the installation, do not unblock
the burner more than twice in a
row. If the burner locks for a third time,
contact the customer service.
NB: after each operation:
• under normal operating conditions
(doors closed, hood fitted, etc.), check
combustion and check the individual
lines for leaks.
• Record the results in the relevant
documents.
EBCU diagnostic
tool must be used
to read the faults
by service
personell.
WARNING
DANGER
WARNING
Содержание MAX GAS 120 P
Страница 54: ...54 www ecoflam burners com 420010372804 RU 1 2 3 2 3 5 A B A B 1 WARNING 30 C 5 1 2 3 WARNING DANGER...
Страница 55: ...55 www ecoflam burners com 420010372804 RU 1 2 3 4 E BCU WARNING DANGER WARNING...
Страница 65: ...65 www ecoflam burners com 420010372804 EN IT FR ES RU...
Страница 66: ...66 www ecoflam burners com 420010372804 EN IT FR ES RU...
Страница 67: ...67 www ecoflam burners com 420010372804 EN IT FR ES RU...