background image

9

Installation Instructions

4. COLD WATER PIPE GROUNDING

CAUTION:

The house cold water pipe (metal only) is

often used as a ground for the house elec-

trical system,  The 3-valve bypass type of

installation, shown in Figure 6, will maintain

ground continuity.  If you use a plastic

bypass valve at the unit, continuity is bro-

ken.  To restore the ground, do the follow-

ing:

a

. Install a #4 copper wire across the removed section

of main water pipe, securely clamping it at both

ends (See Figure 12) - parts not included.

NOTE:

Check local plumbing and electrical codes for

proper installation of grounding.  The installa-

tion must conform to them.  In Massachusetts,

plumbing codes of Massachusetts shall be

conformed to.  Consult with your licensed

plumber.

5. INSTALL VALVE DRAIN HOSE

a

. Take a length of 5/8” inside diameter garden hose

and attach to the valve drain fitting (See Figure 7 on

page 7).

b

. Locate the other end of the hose at a suitable drain

point (floor drain, sump, laundry tub, etc.).  Check

and comply with local codes.  Refer to Figure 7 on

page 7 if codes require a rigid pipe drain run.

IMPORTANT:

Use high quality, thick wall hose that will

not easily kink or collapse.  The filter will

not backwash properly if water cannot

exit this hose during recharges.

c

. Tie or wire the hose in place at the drain point.

Water pressure will cause it to whip during the back-

wash and fast rinse cycles of recharge.  Also pro-

vide an air gap of at least 1-1/2” between the end of

the hose and the drain point.  An air gap prevents

possible siphoning of sewer water, into the filter, if

the sewer should back up.

d

. If raising the drain hose overhead is required to get

to the drain point, do not raise higher than 8 feet

above the floor.  Elevating the hose may cause a

back pressure that could reduce backwash flow and

proper mineral bed cleaning.

6. FLUSH PIPES, CIRCULATE DISINFEC-

TANT, EXPEL AIR FROM FILTER, AND

TEST YOUR INSTALLATION FOR LEAKS

CAUTION:

To avoid water or air pressure damage to

filter inner parts, be sure to do the following

steps exactly as listed:

a

. Fully open two cold, filtered water faucets nearby

the filter.

b

. Place bypass valve(s) into “bypass” position.  On a

single valve, slide the stem inward to BYPASS (See

Fig. 7 on page 7).  On a 3 valve system, close the

inlet and outlet valves, and open the bypass valve

(See Fig. 6 on page 7).

c

. Fully open the house main water pipe shutoff valve.

Observe a steady flow from both opened faucets.

d

. Place bypass valve(s) into “service”, EXACTLY as

follows. KEEP FILTERED WATER FAUCETS OPEN.

    

=

Single Bypass Valve:

SLOWLY, pull the valve

stem outward to ”service” position, pausing sev-

eral times to allow the filter to pressurize slowly.

    

=

3 Valve Bypass:

Fully close the bypass valve

and open the outlet valve.  SLOWLY, open the

inlet valve,  pausing several times to allow the fil-

ter to pressurize slowly.  The sanitizing bleach

also circulates through the filter.

continued on next page

3. COMPLETE PLUMBING TO AND FROM

THE FILTER

Using the “Typical Installation Illustrations” on page 7

as a guide, observe all of the following cautions while

you connect inlet and outlet plumbing:

=

 Be sure incoming, 

unfiltered water

is directed to

the valve 

INLET

port.

=

 Be sure to install bypass valve(s).

=

 If making a soldered copper installation, do all

sweat soldering before connecting pipes to the filter

fittings.  Torch heat will damage plastic parts.

=

 Use pipe joint compound on all external pipe

threads.

=

 When turning threaded pipe fittings onto plastic fit-

tings, use care not to cross-thread.

=

 Support inlet and outlet plumbing in some manner

(use pipe hangers) to keep the weight off of the

valve fittings.

FIG. 12

Ground Wire

Clamp (2)

Содержание HPF

Страница 1: ...NSAPFXLA tested and certified without media by the Water Quality Association under NSF ANSI Standard 61 for material safety requirements only and NSF ANSI Standard 372 for low lead content Not certif...

Страница 2: ...hold outlet that is in a dry location only grounded and properly protected by an overcurrent device such as circuit breaker or fuse This system is not intended to be used for treating water that is mi...

Страница 3: ...1 1 1 1 Filtering Micron Rating 20 Supply Water pH Limits 6 0 6 8 Capacity 34 000 gal 15 500 gal at 10 psi maximum pressure drop at 35 psi inlet pressure Valve inlet outlet and installation adaptors...

Страница 4: ...ts of tastes and odors and or higher water usages may shorten this time Activated carbon can t be regenerat ed and must be replaced when exhausted see page 16 WATER NEUTRALIZING FILTER All water when...

Страница 5: ...lled indoors Keep the filter out of direct sunlight The sun s heat may soften and distort plastic parts TOOLS PIPE FITTINGS OTHER MATERIALS YOU WILL NEED Plastic inlet and outlet fittings included wit...

Страница 6: ...sh the tank opening with water to clean media particles from the top of the tank Uncover the bottom distributor stand tube 11 Finish filling the tank with water up to the top of the tank IMPORTANT Be...

Страница 7: ...G 5 INSTALLATION USING 3 VALVE BYPASS MAIN WATER PIPE MAIN WATER PIPE INSTALLATION USING INCLUDED BYPASS VALVE CROSS OVER Use if water supply flows from the left Include single or 3 valve bypass Filte...

Страница 8: ...ring Clip Cross section of valve inlet or outlet Bypass valve or plastic adaptor Snap clips into place between larger diameter rings FIG 11 Turn the bypass valve downward if connecting to floor level...

Страница 9: ...ting the hose may cause a back pressure that could reduce backwash flow and proper mineral bed cleaning 6 FLUSH PIPES CIRCULATE DISINFEC TANT EXPEL AIR FROM FILTER AND TEST YOUR INSTALLATION FOR LEAKS...

Страница 10: ...to a 120V 60 Hz electrical outlet Be sure the outlet is always live so it can not be switched off by mistake Installation Instructions 8 PROGRAM THE TIMER See pages 11 12 for instructions to program t...

Страница 11: ...advance the display Hold the buttons down for fast advance 2 When the correct time is displayed press the SELECT button and the display will change to show the next setup screen 2 The default setting...

Страница 12: ...this time as the water heater will refill with unfiltered water FIG 19 VACATION CONTROL 1 Before going on vacation or other long absence press but do not hold the TOUCH HOLD button so that VAC begins...

Страница 13: ...Use the r UP or s DOWN buttons to adjust solu tion draw rinse time from 0 to 255 minutes 3 When the desired draw time is displayed press the SELECT button and the display will change to show the 12 24...

Страница 14: ...he table below explains the choices available for when the auxiliary output will be on dur ing various portions of the recharge cycle FIG 26 SELEC TION NAME AUXILIARY OUTPUT FUNCTION OFF Off Remains o...

Страница 15: ...is difficult to determine exactly when to add more mineral When you have had the filter for a period of time experience will tell you when to add more mineral You can use the instructions following s...

Страница 16: ...the filter from the instal lation adaptors or from the bypass valve Figure 8 page 8 5 Remove the two clamp retainers and two clamp sections that hold the valve to the tank Lift the valve assembly up a...

Страница 17: ...to check flow control See page 22 to check for correct assembly and orientation Backwash flow should be 5 gpm or higher Low water pressure at house faucets Well pump pressure switch set too low Adjust...

Страница 18: ...ronic Control Board PWA TO REMOVE AN ERROR CODE 1 Unplug the power supply 2 Correct the problem 3 Plug the power supply back in 4 Wait for at least 8 minutes while the timer operates the valve through...

Страница 19: ...D button to manually advance the valve into each position and check correct switch operation 4 While in this diagnostic screen the following infor mation is available and may be beneficial for vari ou...

Страница 20: ...Position Switch S SERVICE Valve Cam FIG 38 BR FILL F BRINE DRAW Position Switch Valve Cam FIG 39 Position Switch Valve Cam FIG 40 BW BACKWASH FAST RINSE Position Switch Valve Cam FIG 41 Position Switc...

Страница 21: ...ng 2 3 4 x 3 11 7088855 Top Distributor 12 7105047 Repl Bottom Distributor 13 7092202 Mineral Tank 10 x 47 7113074 Mineral Tank 12 x 54 14 7339141 Catalytic Carbon 1 cu ft Chloramine Chlorine Taste Od...

Страница 22: ...2 Valve Exploded View Wear Strip Seal Cross section View 52 50 53 54 55 51 56 57 58 59 60 61 66 67 78 62 63 64 68 69 65 77 70 83 72 70 71 72 73 74 75 76 79 80 81 82 84 Flow Plug Assembly Assembled Vie...

Страница 23: ...g Wave Washer 67 7185500 Rotor Disc Key No Part No Description 7342712 Drain Plug Kit 1 includes Key Nos 64 68 69 68 Plug Drain Seal 69 Spring 70 7089306 Clip 1 single 2 req 7336428 Clip 1 pack of 20...

Страница 24: ...orce of nature such as but not limited to freezing flood hurricane tornado or earthquake is not covered by this warranty In all such cases regular parts and serv ice charges will apply We assume no wa...

Отзывы: