22
3. Example: CM3H-2228A23
Fig.6
Table 10 Indoor Unit
Serial No.
Model
Indoor Unit 1
CMSH-12QB
Indoor Unit 2
CMSH-12QB
Indoor Unit 3
CMSH-12QB
Table 11 Liquid Refrigerant Pipe
Serial No.
a
b
c
Diameter
Φ
6.35
Φ
6.35
Φ
6.35
Length
20
15
15
The total length of each liquid refrigerant pipe is: a+b+c=20+15+15=50m
Thus, the minimum additional refrigerant charge=(50-15)×0.012=0.42kg
(Note: no additional refrigerant is needed for the liquid pipe within 15m)
4. Additional Refrigerant Charge Record
Table 12 Indoor Unit
No.
Indoor Unit Model
Additional Refrigerant Refrigerant (kg)
1
2
3
.....
N
Total
Table 13 Refrigerant Pipe
Diameter
Total Length (m)
Additional Refrigerant Refrigerant (kg)
Φ
15.9
Φ
12.7
Φ
9.52
Φ
6.35
Total