Table 6 Dimension of the Refrigerant Pipe of the Indoor Unit
Capacity Level of the Indoor Unit
Gas Pipe (mm)
Liquid pipe (mm)
09
、
12
Φ
9.52
Φ
6.35
18
Φ
12.7
Φ
6.35
●
Piping between the Indoor and Outdoor units
1. Refer to Table 7 for the moments of torque for tightening screws.
2. Let the flare end of the copper pipe point at the screw and then tighten the screw by hand.
3. After that, tighten the screw by the torque wrench unit it clatters (as shown in Fig.3).
4. The bending degree of the pipe cannot be too small, otherwise it will crack. And please use a pipe tube bender to
bend the pipe.
5. Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape.
Ordinary Wrench
Pipe
Flare Nut
Pipe
Fig.3
Torque
Wrench
Pipe
Flare Nut
Pipe
Table 7 Moments of Torque for Tightening Screws
Diameter (mm)
Wall Thickness (mm)
Moment of Torque (N.m)
Φ
6.35
≥
0.5
15-30
Φ
9.52
≥
0.71
30-40
Φ
12.7
≥
1
45-50
Φ
15.9
≥
1
60-65
CAUTION!
1. During the connection of the indoor unit and the refrigerant pipe, never pull any joints of the indoor unit by force,
otherwise the capillary pipe or other pipe may crack, which then would result in leakage.
2. The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of it.
CAUTION!
For the MULTI-S inverter air conditioner unit, each pipe should be labeled to tell which system it belongs to avoid mistaken
inaccurate piping.
●
Installation of the Protection Layer of the Refrigerant Pipe
1. The refrigerant pipe should be insulated by the insulating material and plastic tape in
order to prevent condensation and water leakage.
2. The joints of the indoor unit should be wrapped with the insulating material and no gap
is allowed on the joint of the indoor unit, as shown in Fig.4.
CAUTION!
After the pipe is protected well enough, never bend it to form a small angle, otherwise it would crack or break.
●
Wrap the Pipe with Tape
1. Bundle the refrigerant pipe and electric wire together with tape, and separate them from the drain pipe to prevent the
condensate water overflowing.
2. Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall. During the wrapping,
the later circle should cover half the former one.
3. Fix the wrapped pipe on the wall with clamps.
Содержание CM2-H16/4DR2
Страница 1: ...Service manual FREE MATCH 50Hz R32 Models СM2 H16 4DR2 СM3 H22 4DR2 2022 06 ...
Страница 3: ...1 1 Summary and Features Outdoor Unit CM2H 1644A23 CM3H 2228A23 ...
Страница 11: ...9 4 Construction Views 4 1 Outdoor Unit CM2H 1644A23 Unit mm ...
Страница 12: ...10 CM3H 2228A23 Unit mm ...
Страница 27: ...25 8 Exploded Views and Parts List 8 1 Outdoor Unit Model CM2H 1644A23 ...
Страница 29: ...27 Model CM3H 2228A23 ...
Страница 47: ...41 ...