COMFORT DUO RF
4
4-2. PROG copy
Press the
key to select the settings for PROG.
Press the
key to start programming.
Press
Prog Copy function:
Before copying the program, please select any day of
the week and complete entire temperature set points
for each program period of the day. (Read
Programming procedure described in the step 4-1. Set
PROG).
Press
to enter “PROG COPY” function. ‘-From'
MoTuWeThFrSaSu
lit on the LCD (Choosing the
reference-day “from”).
Take the selected day as reference-day for “Copy”
function, and follow the instructions below:
A. Press
to select the reference-day.
B. Press
after reference-day is selected, ‘To' will
lit on LCD.
C. Press
to select the day of the week for the
programs to be copied to.
Press
as confirmation.
D. Repeat the steps by pressing
and
to
select more days to copy the programs to or press
to delete the previously selected day of the
week (flashing).
E. Press
after desired days for “copy” are
completed. The display returns to start PROG
setting mode.
5
Set Differential
Press the
key to select the settings for Operating
mode.
Press
to change between TPI and ANALOGE
operationg mode and press
to select the desired one.
5-1 Analoge operating mode
Once selected the Analoge operating mode, press
key to change value.0.5/1/1.5/2, the default
value is 0.5).
Press
to save the changed value.
5-2 TPI operting mode
CPH: Cicles per hour
Once selected the TPI operating mode, press
key to change CHP value: 3/6/9/12, (the default value is
6).
Press
to save the changed value and change to P-
BAND parameter.
Through this parameter the number of modulation cycles
per hour is selected. In other words, if CPH=6 the
thermostat will do 6 modulation cycles, so each cycle will
last for 10 minutes.
P-BAND: Modulation range
Press again
key to change P-BAND value: 1,5
ºC – 3 ºC (the default value is 1,5 ºC).
Press
to save the changed value.
This parameter selects the temperature range in which
the modulation is activated. For example, if P-BAND=2
the modulating will be activated between the Set
Temperature ±1 ºC.