7.8.1
Operating Device with Touch screen
The operating device is located in a cardboard box next to the electrical connection
box. Remove the control panel from the packaging and install it securely inside in a
dry and dust-protected location. It should not be exposed to direct sunlight. Ensure
that the 4pin cable connection is properly sealed to the wall and the heat pump.
The cable has a length of 10 m and the distance can be extended to a maximum of 30
m.
7.8.2
Cascade
If several heat pumps are to be cascaded, the respective number must be defined on
the control unit.
Up to 8 heat pumps can be controlled.
Overview of the correct settings of microswitch on main board:
Heat pump
SW 2
SW 3
SW 4
#1
OFF
OFF
OFF
#2
OFF
OFF
ON
#3
OFF
ON
OFF
#4
OFF
ON
ON
#5
ON
OFF
OFF
#6
ON
OFF
ON
#7
ON
ON
OFF
#8
ON
ON
ON
SW 1 always remains OFF!
Use hot water sensor and valve from heat pump #1.
7 Installation
35
Installation Manual
Содержание EASYPELL EPA 09
Страница 1: ...Installation Manual Heat pump EASYPELL EPA 09 12 ENGLISH www easypell com 290108_EN...
Страница 27: ...7 7 Fitting the air separator EPA 09 1 4x 2 3 EPA 12 EPA12T 1 4x 2 3 7 Installation 27 Installation Manual...
Страница 30: ...Mainboard EPA 09 30 7 Installation Installation Manual...
Страница 32: ...Mainboard EPA 12 32 7 Installation Installation Manual...
Страница 34: ...Mainboard EPA 12T 34 7 Installation Installation Manual...
Страница 36: ...7 9 Removing the fan 36 7 Installation Installation Manual...
Страница 55: ...10 Power curves maximum Power curves EPA 09 10 Power curves maximum 55 Installation Manual...
Страница 56: ...Power curves EPA 12 56 10 Power curves maximum Installation Manual...
Страница 59: ...11 3 Hydraulic scheme 3 11 Hydraulic diagrams 59 Installation Manual...
Страница 62: ......
Страница 63: ......
Страница 64: ......