38
Value in UI
200
200
Actual parameter value
400°C
400°C
58
Fan 2 as Ambient Minimum
Gases Temperature
FAN2 stop gases temperature (in °C):
If Fan 2 As Chimney is enabled, this parameter is ignored.
If Fan 2 for Room Heating is enabled, this PAR defines the
threshold for FAN2 operation, regardless of the operating
sequence. FAN2 starts when the gases temperature rises
above PAR58, and stops when it drops below PAR58.
59
No Fuel (Error) Gases
Temperature
Temperature for No Pellets Alarm (in °C):
Defines the flue gases temperature threshold for the No
Pellets alarm in the Burning state.
Cleaning
No.
Parameter
Description
60
Fan 1 Blow Cleaning Period
Time between two blow cleanings (in minutes):
During Burning the burning chamber is cleaned periodically.
Every PAR60 minutes the FAN1 blows for PAR61 seconds at
PAR62 speed. During blow cleaning the feeder stops dosing
fuel.
64
Chamber Cleaning Duration
/Rot.
Defines the number of blow cleanings before the
heating device goes to FIRE STOP and performs the
‘’Erato cleaning’’.
65
Ash Extraction Auger Duration
Ash extraction auger activation duration (in seconds):
Defines the duration of the ash extraction auger cleaning
period. The Ash extraction auger (connected to I/O O03) is
active for PAR65 seconds every PAR66 minutes. The Ash and
Chamber Cleaning configuration option must be set.
NOTE: The ash extraction auger does not operate while the
heating device is turned off. It operates only during normal
operation of the heating device.
66
Ash Extraction Auger Period
Ash extraction auger activation period (in minutes):
Defines the period for activating the ash extraction auger.
NOTE: See also the description for PAR65.
Water pump settings
For detailed description of water pump operation refer to chapter
Error! Reference source not found.
on page
Error! Bookmark not defined.
.
No.
Parameter
Description
67
ON Temperature
Water pump turn on temperature (in °C):
Defines the water temperature threshold when the water
pump turns ON.