32
P0016-LI-02.01
Group 04: Link Control
There are 99 Link controlled outputs, which can be assigned to an
output:
No Type & Description
01
Link Control 01
This output type is controlled by a combination of linked inputs.
02-
99
Link Control 02 - 99
As Link Control 01.
To create a link controlled output you must assign link inputs to
the Link Control. The available inputs are:
f
Zone Links
f
Control Timer Links
f
Voice Message Links
f
System Links
f
User Link
The inputs can be assigned to the Link Control to perform either a
logical “OR” function or a logical “AND” function. The logic
function is controlled by the link input number:
001 - 099: Logical “OR” Link inputs.
101 - 199: Logical “AND” Link inputs.
Link Control Example 1
In the first example we will setup “Link Control 01” so that it
activates when zone 1 “OR” zone 2 “OR” zone 3 is active “OR”
user 02 is entered. The figure below show the logic diagram for
this:
Í
Ë
Ì
Ê
Link Control 01
Logic “1”
Logic “1”
Logic “1”
Logic “1”
The four switches represent the link inputs and programmed as
follows:
Location 1901: Zone 01 Link = 001 (Link Control 01 “OR”).
Location 1902: Zone 02 Link = 001 (Link Control 01 “OR”).
Location 1903: Zone 03 Link = 001 (Link Control 01 “OR”).
Location 8502: User 02 Link = 001 (Link Control 01 “OR”).
As the figure above shows the Link Control 01 will be active (logic
1) when any of the input links are closed (active). Now that Link
Control 01 is configured it can be assigned to a panel output or
voice message trigger.
Link Control Example 2
In this example we will setup “Link Control 02” so that it activates
when zone 4 “AND” zone 5 are active “AND” when the system is
armed. The figure below shows the logic diagram for this:
Ë
Ì
Ê
Logic “1”
Link Control 02
The three switches represent the link inputs and are programmed
as follows:
Location 1904: Zone 04 Link = 102 (Link Control 02 “AND”).
Location 1905: Zone 05 Link = 102 (Link Control 02 “AND”).
Location 3904: System Armed Link = 102 (Link Control 02
“AND”).
As the figure above shows, the Link Control 02 will be active (logic
1) only when ALL of the input links are closed (active).
Link Control Example 3
In this example we will setup “Link Control 03” so that it activates
when zone 10 “AND” Control Timer 1 is on “OR” when the system
is in exit mode “OR” when an intruder alarm occurs. The figure
below show the logic diagram for this:
Ì
Í
Ê
Link Control 03
Logic “1”
Logic “1”
Logic “1”
Ë
The four switches represent the link inputs and programmed as
follows:
Location 1910: Zone 10 Link = 103 (Link Control 03 “AND”).
Location 3541: Control Timer 1 Link = 103 (Link Control 03
“AND”).
Location 3935: System Exit Link = 003 (Link Control 03 “OR”).
Location 3909: System Intruder Alarm Link = 003 (Link
Control 03 “OR”).
As the figure above shows the Link Control 03 will be active (logic
1) only when link input 1 and 2 are closed (active) or when either
link inputs 3 and 4 are closed (active).
Group 10: Zone Count
The zone activity count threshold of each zone can be assigned to
an output:
No Type & Description
01 Zone
01
Count
This output type activates when zone 01 activity count reaches
the threshold set by the “Zone Warning” counter. See page 24.
02-
20
Zone 02 - 20 Count
As Zone 01 Count.
Group 20: Zone Mimic
The mimic condition of each zone can be assigned to an output:
No Type & Description
01 Zone
01
Mimic
This output type activates when zone 01 is active and
deactivates when zone 01 is healthy.
02-
20
Zone 02 - 20 Mimic
As Zone 01 Mimic.
Group 30: Zone Alarm
The alarm condition of each zone can be assigned to an output:
No Type & Description
01 Zone
01
Alarm
This output type activates when zone 01 generates an alarm and
deactivates when the alarm is reset.