background image

32 

P0016-LI-02.01 

Group 04: Link Control 

There are 99 Link controlled outputs, which can be assigned to an 
output: 

No   Type & Description 

01 

Link Control 01 

This output type is controlled by a combination of linked inputs.  

02-
99 

Link Control 02 - 99 

As Link Control 01. 

 

To create a link controlled output you must assign link inputs to 
the Link Control. The available inputs are: 

f

 

Zone Links 

f

 

Control Timer Links 

f

 

Voice Message Links 

f

 

System Links 

f

 

User Link 

The inputs can be assigned to the Link Control to perform either a 
logical “OR” function or a logical “AND” function. The logic 
function is controlled by the link input number: 

001 - 099: Logical “OR” Link inputs.   

101 - 199: Logical “AND” Link inputs. 

Link Control Example 1   

In the first example we will setup “Link Control 01” so that it 
activates when zone 1 “OR” zone 2 “OR” zone 3 is active “OR” 
user 02 is entered. The figure below show the logic diagram for 
this:   

Í

Ë

Ì

Ê

Link Control 01

Logic “1”

Logic “1”

Logic “1”

Logic “1”

 

The four switches represent the link inputs and programmed as 
follows: 

  Location 1901: Zone 01 Link = 001 (Link Control 01 “OR”). 

 

Location 1902: Zone 02 Link = 001 (Link Control 01 “OR”). 

 

Location 1903: Zone 03 Link = 001 (Link Control 01 “OR”). 

 

Location 8502: User 02 Link = 001 (Link Control 01 “OR”). 

As the figure above shows the Link Control 01 will be active (logic 
1) when any of the input links are closed (active). Now that Link 
Control 01 is configured it can be assigned to a panel output or 
voice message trigger.  

Link Control Example 2   

In this example we will setup “Link Control 02” so that it activates 
when zone 4 “AND” zone 5 are active “AND” when the system is 
armed. The figure below shows the logic diagram for this:   

Ë

Ì

Ê

Logic “1”

Link Control 02

 

The three switches represent the link inputs and are programmed 
as follows: 

 

Location 1904: Zone 04 Link = 102 (Link Control 02 “AND”). 

 

Location 1905: Zone 05 Link = 102 (Link Control 02 “AND”). 

 

Location 3904: System Armed Link = 102 (Link Control 02 
“AND”). 

As the figure above shows, the Link Control 02 will be active (logic 
1) only when ALL of the input links are closed (active). 

Link Control Example 3   

In this example we will setup “Link Control 03” so that it activates 
when zone 10 “AND” Control Timer 1 is on “OR” when the system 
is in exit mode “OR” when an intruder alarm occurs. The figure 
below show the logic diagram for this:   

Ì

Í

Ê

Link Control 03

Logic “1”

Logic “1”

Logic “1”

Ë

 

The four switches represent the link inputs and programmed as 
follows: 

 

Location 1910: Zone 10 Link = 103 (Link Control 03 “AND”). 

 

Location 3541: Control Timer 1 Link = 103 (Link Control 03 
“AND”). 

 

Location 3935: System Exit Link = 003 (Link Control 03 “OR”). 

 

Location 3909: System Intruder Alarm Link = 003 (Link 
Control 03 “OR”). 

As the figure above shows the Link Control 03 will be active (logic 
1) only when link input 1 and 2 are closed (active) or when either 
link inputs 3 and 4 are closed (active). 

Group 10: Zone Count 

The zone activity count threshold of each zone can be assigned to 
an output: 

No   Type & Description 

01 Zone 

01 

Count 

This output type activates when zone 01 activity count reaches 
the threshold set by the “Zone Warning” counter. See page 24.  

02-
20 

Zone 02 - 20 Count 

As Zone 01 Count. 

Group 20: Zone Mimic 

The mimic condition of each zone can be assigned to an output: 

No   Type & Description 

01 Zone 

01 

Mimic 

This output type activates when zone 01 is active and 
deactivates when zone 01 is healthy.  

02-
20 

Zone 02 - 20 Mimic 

As Zone 01 Mimic. 

Group 30: Zone Alarm 

The alarm condition of each zone can be assigned to an output: 

No   Type & Description 

01 Zone 

01 

Alarm 

This output type activates when zone 01 generates an alarm and 
deactivates when the alarm is reset.  

Содержание EC-P10

Страница 1: ...EC P10 10 20 Zone Intruder Alarm System Installation Manual...

Страница 2: ...20 Zone Bypass Options 21 Zone Chime 21 Zone Soak Test 21 Zone Text 21 Zone Link 21 2 Arming Control 22 Arming Timers 22 Arming Modes 22 Arm Options 1 22 Arm Options 2 23 Arm Keyswitch Control 23 Auto...

Страница 3: ...ink 40 9 Utilities 41 Time and Date 41 User Menus 41 Away Arm A 41 Stay Arm 1 S 41 Stay Arm 2 2 41 Stay Arm 3 3 41 Walk Test 11 41 Test Bell Outputs 12 41 Do Test Call 13 41 View Event Log 21 41 Print...

Страница 4: ...4 P0016 LI 02 01 1 System Overview System Configuration...

Страница 5: ...Trouble Bypass Alert and Alarm are also provided Other features include f 4 wire connection using standard alarm cable f Internal sounder f Backlit keyboard EC LCD Remote Keypad The LCD keypad featur...

Страница 6: ...he control panel on a flat plumb wall using at least three appropriate screws The rear casing has been designed with a central key hole slot so that mounting is possible without removing the Printed C...

Страница 7: ...se Fuse T500mA L E N To Power Supply Module 4 Mains Supply Cable Entry The mains supply cable must be routed into the control panel housing via this cable entry 5 Communication Module An optional Ecli...

Страница 8: ...n auto resetting fuse PTC rated at 1 1 Amp 8 Speaker These terminals are used for driving 16 extension loudspeakers see page 12 9 Bell Tamper Return This terminal is connected to the tamper return con...

Страница 9: ...s 750mA This is the recommended charge rate for a 17Ah standby battery The system will fully recharge a flat battery within 24hours 18 Battery On Kick Start When powering the system from battery only...

Страница 10: ...ther and wired into the terminal at the control panel only The maximum recommended distance for devices when using standard 7 0 2 alarm cable is f 250m for each branch when using the star parallel con...

Страница 11: ...e EC P10 provides 10 zones for connecting detection devices such as movement sensors and magnetic door contacts Each zone is fully programmable to allow for maximum flexibility see page 19 for Zone Pr...

Страница 12: ...Com 1 Detector 2 Detectors Alarm Tamper E O L Alarm Tamper Alarm Tamper E O L 4K7 2K2 4K7 4K7 2K2 Triple EOL This wiring configuration should be used when connecting detection devices that support tri...

Страница 13: ...ct this terminal to the strobe input on the external sounder strobe unit Control Panel 12V TR 0V 1 2 External Sounder Tamper 0V 12V Suppy Bell ve Strobe ve Panel Outputs 1 5 The control panel has five...

Страница 14: ...will show En Engineers Menu Location LED LCD f Program the system as described in the next section Programming the Control Panel f Carry out a walk test as described on page 41 Remember that some pow...

Страница 15: ...one Text 9 Zone Links 19 2 Arming Options 0 Full Arm Options 1 Stay Arm 1 Options 2 Stay Arm 2 Options 3 Stay Arm 3 Options 22 3 System Configuration 1 System Timers 2 System Counters 3 Hardware Optio...

Страница 16: ...ech Dialler Engineers Menu 7400 UDL Options Engineers Menu 8100 User Codes Engineers Menu 9001 Adjust Clock A S Section start location Section description A S Next up Previous down Select section Engi...

Страница 17: ...number The figures below show the programming procedure for both LED and LCD remote keypads Bit Toggle Selection LED Keypad En 1 3 0 1 Enter Engineers code Enter location No e g 1301 Press to display...

Страница 18: ...rrent value are displayed 0 Enter required value e g 35 String Edit Number Mode This type of data entry is used for entering a long string of numbers such as telephone and account numbers The figures...

Страница 19: ...vation of the zone will start the Entry 1 Delay timer for the relevant arm mode 02 Final Exit 2 Use this zone type for an alternative entry exit detector The zone can be activated during the exit mode...

Страница 20: ...tive for longer than the warning delay time see page 24 for details 21 Log Monitor Use this zone type for monitoring devices that require an event log entry This zone type generates a log entry if act...

Страница 21: ...ctive and reinstated when the Bypass Key is secure Off The zone is not bypassed when a Bypass Key is operated 7 Cleaner On The zone is bypassed when a cleaner code is entered Off The zone is not bypas...

Страница 22: ...ter the activation of a Final Exit 1 or Final Exit 2 zone type e g after the front door is opened the closed 1 Timed Exit When the exit mode is started the system will arm after the Exit Delay timer h...

Страница 23: ...ch Options 2243 Stay Arm 2 Keyswitch Options 2343 Stay Arm 3 Keyswitch Options Entry Mode Bit Toggle Selection see page 17 1 Silent Arm On The exit tone remains silent during exit mode when a keyswitc...

Страница 24: ...ce Required event is generated Default 0 weeks 10 Confirmation Period This timer controls the duration 0 255 minutes in which a confirmed alarm event can be generated When the system is armed and an i...

Страница 25: ...tage is not monitored 4 Battery Presence On The standby battery is monitored for its presence Off The standby battery is not monitored 5 Mains AC On The mains supply is monitored for its presence Off...

Страница 26: ...pse UDL software and uploaded into the control panel Alternatively voice messages can be recorded from a telephone handset Activate by Link Control The Link Control is the logical output trigger that...

Страница 27: ...lt 29 Control Panel Box Tamper 30 Bell Tamper 31 Engineer on Site 06 System Armed Alarm 07 Bell 08 Strobe 09 Intruder Alarm 10 Confirmed Alarm 32 Detector Reset 33 Switched 12V 34 System Low Volts 35...

Страница 28: ...Keypad Tamper Enabled On The lid tamper on the selected keypad is monitored Off The lid tamper on the selected keypad is not monitored Keypad Options 2 This second set of options controls how the sel...

Страница 29: ...The expander generates chime tones Off The expander will not generate chime tones 4 Entry Tones On The expander generates entry tones Off The expander will not generate entry tones 5 Exit Tones On Th...

Страница 30: ...ed output activates for the duration of the Pulse 3 Time system timer see page 24 If Delay 1 and Delay 2 options are enabled then the selected output activates after the delay set by the Delay 3 Time...

Страница 31: ...the system is reset 33 Detector Latch This output type is used to latch the alarm condition on detection devices that have a latch input 34 System Low Volts This output type activates when a low volta...

Страница 32: ...ree switches represent the link inputs and are programmed as follows Location 1904 Zone 04 Link 102 Link Control 02 AND Location 1905 Zone 05 Link 102 Link Control 02 AND Location 3904 System Armed Li...

Страница 33: ...er end should be connected to the selected control panel communication port 1 Printer This mode configures the selected communication port for printer operation Use this mode when using a terminal pro...

Страница 34: ...ccept the message IP Configuration These options allow the IP details to be configured and are required when using the EC COM IP module Locations 6401 IP Address 6402 Subnet Mask 6403 Gateway Address...

Страница 35: ...d for each ARC Locations 7031 to 7034 ARC 1 to 4 Protocol Options Entry Mode Bit Toggle Selection see page 17 1 Switch to Next ARC on failed Attempt On The on board communicator switches to the next A...

Страница 36: ...to 7094 ARC 1 to 4 IP Port Number Entry Mode String Edit Number Mode see page 18 Options Auto Test Call Period The on board communicator can be programmed to send a test call event to the ARC This opt...

Страница 37: ...re Channel 6 14 On For location 7202 channel 6 is enabled for location 7242 channel 14 is enabled Off For location 7202 channel 6 is disabled for location 7242 channel 14 is disabled 7 Restore Channel...

Страница 38: ...indicates the calling method 1 Dial Using Telephone No 1 2 Dial Using Telephone No 2 The call attempts are controlled by how many digits are entered Here are some typical examples 1122 Dial four times...

Страница 39: ...gits are entered Here are some typical examples 111 Attempt to call back the remote UDL computer three times using only PSTN 1212 Attempt to call back the remote UDL computer four times alternating be...

Страница 40: ...arm the system If the system was armed by another user type and a cleaner code is entered whilst the system is armed or during the entry procedure the zones that have the Cleaner attribute are bypass...

Страница 41: ...er a valid user code Walk Test 11 Selecting this option allows the detection zones to be tested without causing an alarm As each zone is activated the keypad generates an acknowledgment tone and the z...

Страница 42: ...d by zone GG 01 TR Tamper zone restore GG 2 1 FltA Fault alarm activated by zone GG 2 1 01 FltR Fault on zone has restored GG 0 MA Mask alarm activated by zone GG 0 01 MR Mask alarm on zone has restor...

Страница 43: ...as restored 25 20 AFAL The auxiliary 12V fuse has gone open circuit electronic fuse 25 20 01 AFAR The auxiliary 12V fuse has restored 11 6 20 BFAL The battery fuse has gone open circuit electronic fus...

Страница 44: ...2 1 OPF The control panel has detected a fault on panel output 21 21 G 01 OPR The fault on panel output has restored X 1 GG CLOS Cleaner user number is on site Cleaner zones are bypassed X 1 GG CLoS...

Страница 45: ...r has detected a fault with the telephone line PT The box tamper on the control panel has activated BT The bell tamper on the control panel has activated CE Call engineer to reset the system 3 2 CR Th...

Страница 46: ...rd and dispose of the battery at an official collection point for batteries Physical Dimensions 280 0mm x 255 0mm x 95 0mm Housing 3mm Polycarbonate Packed Weight 975g EC LED Remote Keypad Electrical...

Страница 47: ...opean Union EU Low Voltage Directive LVD 2006 95 EC EMC Conforms to European Union EU Electro Magnetic Compatibility EMC Directive 2004 108 EC Security Conforms to EN 50131 1 and EN 50131 3 Grade 2 En...

Страница 48: ...Technical Support Email support zetaalarmsystems com...

Отзывы: