background image

13

BrightFire 200, V1, Operating Instructions, Edition 09.15

Maintenance and 
Troubleshooting

Preventative maintenance is the key to a reliable, safe
and efficient system. The following are suggested
guidelines for periodic maintenance. Burners in severe
environments or operational conditions should be
checked more frequently.

NOTE:

 The periodic, monthly, and yearly lists are an

average interval. If your environment is dirty, the intervals
may be shorter. Check with local authorities having
jurisdiction regarding their recommended maintenance
schedules.

Periodic Checklist

Remove and inspect the burners at least once per month,
paying close attention to any build-up/degradation of the
burner nozzles.

1. Frequently monitor flame patterns for flames that 

appear to be deflected, abnormal, or impinging on 
refractory surfaces. These are signs of dirty nozzles or 
blocks.

2. Cooling air pressure should be monitored daily to 

ensure proper tip cooling is maintained.

NOTE:

 Excessive cooling air pressure may create

recirculation in the burner block and cause fouling. If
frequent burner block fouling is an issue, reduce the
cooling air pressure, making sure to not allow cooling air
pressure to go below 2 psi (138 mbar) or damage to the
burner nozzles may occur.

3. Burner gas flow and pressure should be monitored 

daily. Irregularities in flow or pressure may indicate a 
dirty burner or block.

4. Regular port flue gas readings should be taken to 

ensure proper air/gas ratios are being maintained. Flue 
gas irregularities may indicate plugging of the 
regenerator ports, instrumentation issues, or furnace 
wear allowing infiltration of ambient air. A side to side 
bias in the ratios may be required.

5. Check the rear packing nuts to verify tightness to 

prevent gas leaks. If the packing nuts bottom out, 
contact the burner body, and cannot be tightened any 
further, the packing needs to be replaced due to wear 
from adjusting the area and flow valves or removing the 
gas tube insert.

Monthly Checklist

1. Clean all burner nozzles on a routine bases once per 

month and when required by flame appearance, 
making sure the burner nozzles are not damaged or 
distorted.

2. Test all the system alarms for proper response signals.

3. Check for the proper operation of ventilating 

equipment.

4. Test the manual gas shut-off valves for proper 

operation.

Yearly Checklist

1. Test (leak test) safety shut-off valves for tightness of 

closure.

2. Test pressure switch settings by checking switch 

movements against pressure settings and comparing 
these with the actual impulse pressure..

3. Clean and inspect all burners.

Instructions for Cleaning

NOTE:

 A matching spare burner can be used to replace a

burner in need of cleaning to minimize furnace disruption
and eliminate the need to plug the burner block during
cleaning.

NOTE:

 Only remove a burner during the off-firing cycle.

1. Shut off local gas and cooling air valve supplying the 

burner to be cleaned.

2. Disconnect gas and cooling air hoses at the burner.

3. Loosen t-bolt or split ring clamp and remove burner 

from the bracket.

4. Inspect the socket plate and carefully clean out any 

debris using a steel rod.

  Molten glass is electrically conductive. DO NOT

make contact with glass surface when cleaning
burner blocks.

CAUTION

5

Содержание BrightFire 200 series

Страница 1: ...Eclipse BrightFire 200 Burners BRT Size G M and B Version 1 Operating Instructions Edition 09 15...

Страница 2: ...and Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection...

Страница 3: ...l of Components 6 BrightFire 200 Adjustable Burners 7 Gimbal Mounting Bracket Installation 7 Pre Start Considerations 7 BrightFire 200 Installation and Start Up During Initial Heat Up Furnace 8 Bright...

Страница 4: ...ncreased flame control and burner flexibility Lower NOX emissions Compatible with current mounting bracket for easy installation Compatible with current BrightFire gas and cool ing air connections for...

Страница 5: ...er equipment installed under the furnace port Eclipse recommends installing a safety guard around moving parts Eclipse recommends considering any area with moving mechanical parts a restricted area Th...

Страница 6: ...ks from UL FM CSA European EN 746 2 with CE mark from TuV Gastec Advantica Electrical Wiring All the electrical wiring must comply with all applicable local codes and or standards such as NFPA Standar...

Страница 7: ...termined from the furnace and port information Gimbal Mounting Bracket Installation NOTE For additional info on the Gimbal Mounting Bracket refer to Info Guide 1113 1 Set all bracket adjustments to ze...

Страница 8: ...main burners is increased the heat up burner input is decreased to maintain the heat up schedule until the heat up burner can be removed Figure 3 1 Typical Installation Under port Figure 3 2 Typical...

Страница 9: ...ngement incorporates two burners per port Both burners of any given port should have equal gas flow and be adjusted in pairs when balancing gas flow On a typical under port fired furnace either side p...

Страница 10: ...et the main gas flow control to manual and open to 10 15 7 Establish gas and cooling air supply up to the local shut off valves 8 Beginning with one burner on the off firing side of the furnace discon...

Страница 11: ...tation of the adjustment knob will lengthen the flame while moving the adjustment forward clockwise rotation of the adjustment knob will shorten the flame To read the indicator rod positions for the a...

Страница 12: ...ed further from the port opening while maintaining lower NOX emissions Converting BrightFire 200 from Gas to Oil Firing NOTE If firing heavy fuel oil the oil must be conditioned to maintain a viscosit...

Страница 13: ...ate plugging of the regenerator ports instrumentation issues or furnace wear allowing infiltration of ambient air A side to side bias in the ratios may be required 5 Check the rear packing nuts to ver...

Страница 14: ...and nut but do not tighten 20 Insert the inner gas tube through the rear of the burner until the end is flush with the area adjustment lug 21 Tighten the inner gas tube locking nut and the packing gla...

Страница 15: ...illimeter mm inch in 3 94 x 10 2 MJ Nm Btu ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 0...

Страница 16: ...Eclipse Inc All Rights Reserved...

Отзывы: