11
Eclipse Packaged Gas BoostPak, V2, Installation Guide 630-2, 6/22/2010
MH Models Temperature
Control Settings
SETUP
FUNCTION
FACTORY
ALGOR
CTRALG
PDMR
_______________
TUNING
PB
6
_______________
MR
45
_______________
RATE
0
_______________
OUTALG
OUTALG
RLY
_______________
INPUT1
IN1TYP
JL
_______________
BRNOUT
UP
_______________
CONTRL
ACTION
DIR
_______________
OPTION
AUXOUT
OUT
_______________
ALARMS
A1S1TY
DE
_______________
A1S1VA
5.0
_______________
A1S1HL
HIGH
_______________
ALHTST
0.3
_______________
Controller Set Point:
120
_______________
Parameters not listed here are set at default values found in Installation Guide 925.
MH Models Rotary
Actuator Settings
PARAMETER
CODE
FACTORY
LF
15
T
0
_______________
HF
15
S
90
_______________
LO
12
T
0
_______________
(C6)
6
6
_______________
(C0)
10
10
_______________