Material
Attenuation
Wood
0 - 10%
Plaster
0 - 10%
Glass
0 - 10%
Brick
5 - 35%
MDF
5 - 35%
Ferroconcrete
10 - 90%
Metal
90 - 100%
Aluminum
90 - 100%
Wireless System Layout Hints
Avoid locating transmitters and receivers on the same wall.
Avoid locating transmitters and receivers where the telegrams must penetrate
walls at acute angles. This increases the material the telegram must pass through
reducing the signal power.
Avoid large metal obstructions as they create radio shadows. Place receivers in
alternate locations to avoid the shadow or use repeaters to go around the obstacle.
Do not locate receivers close to other high frequency transmitters.
Leave at least 3’ between the receiver and any other source of interference
including, ballasts, LED drivers, computers, video equipment, Wi-Fi/LAN
routers, GSM modems and monitors. Transmitters are not affected by these
sources of interference.
echo
flex
Powered by ETC
Echoflex Solutions, Inc.
#1, 38924 Queens Way | Squamish | BC | Canada | V8B 0K8
Toll Free: 888-324-6359 | Phone: (778) 733-0111 | Fax: (604) 815-0078
Email: [email protected] | www.echoflexsolutions.com
Copyright 2015-2017 Echoflex Solutions, Inc. | Specifications subject to change without notice.
Document 8DC-5543 | Revision 1.6| 8188M21-5543-1
| Rev E
Agency Listings and Compliance
CEC Title 24 Compliant
Built in an ISO9001 certified facility
FCC Part 15.231
(902 MHz models only)
Contains FCC ID: TCM300U
The enclosed device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(I.) this device may not cause harmful interference and
(ii.) this device must accept any interference received, including
interference that may cause undesired operation.
IC RSS-210
(902 MHz models only)
Contains IC: 5713A-STM300U
CE (
868 MHz models only
)
CE Marking
ARIB STDT108
(
928MHz models only
)
Complies with the Japanese radio law and is certified according to ARIB STDT108.
This device should not be modified (otherwise the granted designation
number will become invalid)
Material
Radio Range-typical
Line of sight:
80’ (24m) corridors
Line of sight:
150’ (46m)open halls
Plasterboard:
80’ (24m) through 3 walls
Brick:
33’ (10m) through 1 wall
FerroConcrete:
33’ (10m) through 1 wall
Ceiling:
not recommended