Echoflex Installation Guide

Vacancy Sensor

Prepare for Installation

Ceiling-mount sensors are intended for installation to a finished ceiling
surface, soft ceiling tile mounted, or attached to a round or octagonal fixture
junction box.

Compliance

cULus Listed

CE compliant

For use with Echoflex Elaho Control Systems, powered by an Elaho station
power supply.

Environment

Ambient

For indoor, commercial controls use only. Operating temperature 0-40°C
(32-104°F), humidity maximum 90% (non-condensing).

Location

Echoflex recommends paying special attention to the installation
environment:

The sensor must have an unobstructed view of the room. Do not
mount behind or near tall cabinets, shelves, hanging light fixtures, etc.

Do not install the sensor within eight feet from an HVAC airflow
duct/vent.

Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms. If the installation location cannot avoid these
conditions, portions of the lens can be masked to block the sensor
view of these undesired areas. See

Lens Masking on page 11

.

Wire Specification

The Vacancy Sensor connects to the EchoConnect communication bus.
EchoConnect is a bi-directional protocol that uses one pair of wires (data +
and data -) for both data and power. Echoflex recommends using Belden
8471 Class 2 wire (or approved equal - see the Echoflex cable cross database

echoflexsolutions.com/files/Elaho_Data_Cable_Wire_Specs

for equal

alternatives). The total combined length of an EchoConnect wire run using
Belden 8471 may not exceed 500 m (1,640 ft), with a maximum distance of
400 m (1,312 ft) between any two devices.

Vacancy Sensor

Page 2 of 12

Echoflex

Содержание Elaho E-VAC

Страница 1: ...cy Sensor provides 360 degree coverage of the installed location and is available in these models Model Coverage m 2 Coverage ft 2 E VAC SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m 2 at 6 7 m 800 ft 2 at 12 ft E VAC Large Room 167 m 2 at 2 4 m 1 800 ft 2 at 8 ft 279 m 2 at 6 7 m 3 000 ft 2 at 12 ft E VAC HC High Ceiling 28 m 2 at 2 4 m 300 ft 2 at 10 ft 650 m 2 at 12 2 m 7 000 ft 2 at ...

Страница 2: ...ight feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or adjacent rooms If the installation location cannot avoid these conditions portions of the lens can be masked to block the sensor view of these undesired areas See Lens Masking on page 11 Wire Specification The Vacancy Sensor c...

Страница 3: ...at is provided with the Cat5 Termination Kit 8186A1207 for information to terminate Cat5 wiring Not all topologies are supported using Cat5 careful planning is required to ensure the proper termination kits are available and the wire is pulled appropriately Supplies The following supplies are provided with the sensor EchoConnect and ESD ground wire pigtails Soft ceiling tile adapter Mounting screw...

Страница 4: ...oConnect pigtail as well as any continuing data EchoConnect wire together and secure with a wire nut c Repeat the above step for the data EchoConnect wire typically white and for the ESD ground wire typically green yellow using a new wire nut for each termination type 3 Orient the flat side of the mounting plate to the junction box and pull the EchoConnect wires or terminated pigtail from the junc...

Страница 5: ...sensor in series with other sensors or stations continuing the data run use the provided EchoConnect and ESD ground wire pigtails Termination connectors are not provided If you are not continuing the data run direct termination to the sensor controller is recommended skip this step and proceed to step 3 a Strip each wire to the appropriate length depending on the wire nut or other termination used...

Страница 6: ... and then bend each tine over in opposite directions for a secure fit on the unfinished side of the ceiling tile 5 Terminate EchoConnect and ESD ground wires to the terminal block on the sensor controller Torque each terminal 3 1 3 5 in lb a Strip each wire 8 mm 5 16 in b Insert the data EchoConnect wire typically white into the data terminal and secure c Insert the data EchoConnect wire typically...

Страница 7: ...iliary A buttons and their related LEDs are not used and have no functionality on the Responsive Vacancy Sensor Set Space and Address Two rotary switches on the sensor electronics provide for Space and Address assignment for the sensor By default these switches are set to Space 1 Address 1 Commands are shared by all devices within a given space 1 Set the Space rotary switch to the desired number 1...

Страница 8: ... On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and Switch 4 is Off Auto Both switches are On See Vacancy Timeout on page 10 5 PIR Detection LED When set to On default the occupancy detection LED illuminates the...

Страница 9: ...uration is not allowed and no events are triggered Configuration Basic When the sensor is in Basic configuration mode DIP switch 2 set to Off the sensor will activate a Space Off command when vacancy is detected Custom When functionality other than Space Off is required place the sensor in Custom configuration mode DIP switch 2 set to On Customization of the sensor and all actions are configured u...

Страница 10: ... ends the grace period begins When the sensor detects vacancy the vacancy timeout period begins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period after a vacancy timeout occurs During this grace period if the sensor detects occupancy it will turn on or res...

Страница 11: ...rtened to ten seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detection is enabled any sound detected will illuminate the lens green 4 Adjust the lens masking if installed blocking certain areas of the installed space from sensor detection See Lens Maskin...

Страница 12: ...m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling Lens Side View 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft 0 12 2 m 40 ft 9 1 m 30 ft 6 1 m 20 ft Vacancy Sensor Page 12 of 12 Echoflex ...

Отзывы: