Echoflex Installation Guide
Vacancy Sensor
Walk Test
The sensor offers a Walk Test mode, which shortens the vacancy timer to ten
seconds and allows for simple and quick verification of the sensor’s coverage
and range in the installed space.
Auxiliary
button
Walk Test
button
1. Prepare the site for configuration.
a. Make certain the sensor and lighting loads are powered and
connected for control by the Elaho control system.
b. You will need direct access to the sensor in order to place it into
Walk Test mode.
2. Press the Walk Test button on the sensor to enable the Walk Test
feature. A green LED will flash, indicating Walk Test is enabled and the
vacancy timer will be shortened to ten seconds.
3. Move throughout the space including corners and areas that may be
obscured from line of sight to the sensor. Each time the sensor detects
movement, the lens illuminates red. If acoustic detection is enabled,
any sound detected will illuminate the lens green.
4. Adjust the lens masking, if installed, blocking certain areas of the
installed space from sensor detection. See
5. Walk Test mode automatically exits and the sensor returns to normal
operation after five minutes. You can also manually terminate by
pressing the Walk Test button again.
Lens Masking
Lens masks are provided in the packaging for your convenience. Use this to
block a section of the lens from detecting occupancy. To attach, cut to the
desired size, remove the backing and stick it on the sensor lens, covering the
desired sections.