background image

Echoflex Installation Guide

Vacancy Sensor

Walk Test

The sensor offers a Walk Test mode, which shortens the vacancy timer to ten
seconds and allows for simple and quick verification of the sensor’s coverage
and range in the installed space.

Auxiliary 

button

Walk Test

button

1. Prepare the site for configuration.

a. Make certain the sensor and lighting loads are powered and

connected for control by the Elaho control system.

b. You will need direct access to the sensor in order to place it into

Walk Test mode.

2. Press the Walk Test button on the sensor to enable the Walk Test

feature. A green LED will flash, indicating Walk Test is enabled and the
vacancy timer will be shortened to ten seconds.

3. Move throughout the space including corners and areas that may be

obscured from line of sight to the sensor. Each time the sensor detects
movement, the lens illuminates red. If acoustic detection is enabled,
any sound detected will illuminate the lens green.

4. Adjust the lens masking, if installed, blocking certain areas of the

installed space from sensor detection. See

Lens Masking below

.

5. Walk Test mode automatically exits and the sensor returns to normal

operation after five minutes. You can also manually terminate by
pressing the Walk Test button again.

Lens Masking

Lens masks are provided in the packaging for your convenience. Use this to
block a section of the lens from detecting occupancy. To attach, cut to the
desired size, remove the backing and stick it on the sensor lens, covering the
desired sections.

Vacancy Sensor

Page 11 of 12

Echoflex

Содержание Elaho E-VAC-SR

Страница 1: ...y Sensor provides 360 degree coverage of the installed location and is available in these models Model Coverage m 2 Coverage ft 2 E VAC SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m 2 at 6 7...

Страница 2: ...ght feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or adjacent rooms If the insta...

Страница 3: ...t is provided with the Cat5 Termination Kit 8186A1207 for information to terminate Cat5 wiring Not all topologies are supported using Cat5 careful planning is required to ensure the proper termination...

Страница 4: ...Connect pigtail as well as any continuing data EchoConnect wire together and secure with a wire nut c Repeat the above step for the data EchoConnect wire typically white and for the ESD ground wire ty...

Страница 5: ...ensor in series with other sensors or stations continuing the data run use the provided EchoConnect and ESD ground wire pigtails Termination connectors are not provided If you are not continuing the d...

Страница 6: ...and then bend each tine over in opposite directions for a secure fit on the unfinished side of the ceiling tile 5 Terminate EchoConnect and ESD ground wires to the terminal block on the sensor control...

Страница 7: ...liary A buttons and their related LEDs are not used and have no functionality on the Responsive Vacancy Sensor Set Space and Address Two rotary switches on the sensor electronics provide for Space and...

Страница 8: ...On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4...

Страница 9: ...ration is not allowed and no events are triggered Configuration Basic When the sensor is in Basic configuration mode DIP switch 2 set to Off the sensor will activate a Space Off command when vacancy i...

Страница 10: ...ends the grace period begins When the sensor detects vacancy the vacancy timeout period begins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a...

Страница 11: ...tened to ten seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If aco...

Страница 12: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Отзывы: