Echoflex Installation Guide
Vacancy Sensor
Note:
All control wiring should be installed and terminated by a
qualified installer and should follow standard wiring installation
practices. Leave approximately 25.4 cm (10 in) of wiring in the back
box for connection and to allow slack for future service needs.
Note:
Echoflex requires that all stations and devices be grounded for
ESD protection. Pull an additional 2.5 mm
2
(14 AWG) wire for
grounding when control wires are not installed in grounded metal
conduit.
Note:
When using Category 5 (or equivalent) cable on the
EchoConnect communication bus, please note the following:
•
Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the Cat5
Termination Kit (8186A1207) for information to terminate
Cat5 wiring.
•
Not all topologies are supported using Cat5; careful planning
is required to ensure the proper termination kits are available
and the wire is pulled appropriately.
Supplies
The following supplies are provided with the sensor:
•
EchoConnect and ESD ground wire pigtails
•
Soft ceiling tile adapter
•
Mounting screws, 8-32 x 1 3/4”
•
Lens masks
Installation
Note:
Installation must follow all national and local codes for
electrical equipment. NEC Class 2 product to be wired in accordance
to NEC Article 725 and local jurisdiction requirements.
The ceiling-mount sensor is provided with a mounting plate that can be
mounted to a junction box, finished ceiling, or soft ceiling tile. Determine the
installation method and follow the detailed instructions:
•
Junction Box or Surface Installation on the next page
•
Soft Ceiling Tile Installation on page 5
Vacancy Sensor
Page 3 of 12
Echoflex