Echoflex Installation Guide

Dual Tech Occupancy Sensor

2. Press and release the Auxiliary [A] button the number of times that

corresponds to the preset that you want to use. For example, press
the [A] button eight times to set Preset 8. The LED flashes the
number of the preset used.

3. Press and release the [MODE] button to save the current setting.

Operation

Dual Technology

When both PIR and acoustic detection are used, the following logic is
used:

• When the space is vacant, PIR detection and manual control can

switch the state to occupied.

• When the space is occupied, PIR, acoustic detection, and manual

control can reset the vacancy timeout.

• When occupancy in the space has only been triggered by acoustic

detection for 60 minutes, acoustic detection is disabled until the
next PIR detection event.

PIR (only) Detection

When acoustic detection is disabled (DIP switch 6 set to On), the
following logic is used:

• When the space is vacant, PIR detection and manual control can

switch the state to occupied.

• When the space is occupied, PIR detection and manual control can

reset the vacancy timeout.

Vacancy Timeout

Vacancy timeout is the amount of time the sensor waits to take action
after no movement is detected. By default, vacancy timeout is set to 15
minutes (indicated by DIP switch 3 set to Off and 4 set to On; see

DIP

Switches on page 7

). When the vacancy timeout ends, the grace period

begins.

When the sensor detects vacancy, the vacancy timeout period begins. If
the sensor does not detect occupancy again during the vacancy timeout
period, the lights turn off and a 30 second grace period begins.

Grace Period

The sensor features a 30 second grace period after a vacancy timeout
occurs. During this grace period, if the sensor detects occupancy, it will
turn on or restore the previous lighting condition.

Auto Vacancy Timeout

The “Auto” vacancy timeout setting varies the vacancy timeout between
5 and 30 minutes depending on how often it identifies an occupancy
trigger after a vacancy timeout occurs (during the grace period).

Dual Tech Occupancy Sensor

Page 9 of 12

Echoflex

Содержание E-DOC-C-SR

Страница 1: ...ensor offers 360 degree coverage with optimized lens options to accommodate small spaces large spaces and spaces with high ceilings Model Coverage m2 Coverage ft2 E DOC C SR Small Room 41 8 m 2 at 2 4...

Страница 2: ...installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not ins...

Страница 3: ...he back box for connection and to allow slack for future service needs Note Echoflex requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for gr...

Страница 4: ...nting location junction box or finished surface Strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sens...

Страница 5: ...ial from marked access hole c Pull all incoming wires through the access holes of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on...

Страница 6: ...tion on page 8 Note When the sensor is placed into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches...

Страница 7: ...used Sensor actions can be adjusted using the program MODE button See Configuration on page 8 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 3...

Страница 8: ...associated LEDs Custom A sensor that is set for Custom configuration mode DIP switch 2 set to On the default setting can be customized using the ElahoAccess App For more detailed information about cu...

Страница 9: ...ection and manual control can switch the state to occupied When the space is occupied PIR detection and manual control can reset the vacancy timeout Vacancy Timeout Vacancy timeout is the amount of ti...

Страница 10: ...conds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detection...

Страница 11: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Страница 12: ...Echoflex Installation Guide Dual Tech Occupancy Sensor Dual Tech Occupancy Sensor Page 12 of 12 Echoflex...

Отзывы: