Echoflex Installation Guide

Dual Tech Occupancy Sensor

Installation

Note:

Installation must follow all national and local codes for

electrical equipment. NEC Class 2 product to be wired in
accordance to NEC Article 725 and local jurisdiction requirements.

The ceiling-mount sensor is provided with a mounting plate that can be
mounted to a junction box, finished ceiling, or soft ceiling tile. Determine
the installation method and follow the detailed instructions:

Junction Box or Surface Installation below

Soft Ceiling Tile Installation on the facing page

Junction Box or Surface Installation

1. Pull the Belden 8471 (or

equivalent) and one 2.5 mm

2

(14 AWG) ground wire to the
mounting location (junction
box or finished surface). Strip
each wire 11 mm (7/16 in).

2. Temporarily remove the sensor

cover to gain access to the
configuration switches and
mounting access holes. Hold
the sensor in one hand while
gently twisting the cover
clockwise.

3. Connect the EchoConnect

wires from the sensor to the
installed wires.

a. Connect the data– EchoConnect wire (black) from sensor to the

incoming data– EchoConnect wire (typically black) using a
WAGO wire termination connector.

b. Repeat the above step for the data+ EchoConnect wire (white)

and again for the ESD ground wire (green/yellow), using a new
WAGO connector for each termination type.

4. Orient the flat side of the sensor to the junction box or surface and

secure it in place using the screws provided (both short and long
screws are provided for installation convenience).

Dual Tech Occupancy Sensor

Page 4 of 12

Echoflex

Содержание E-DOC-C-SR

Страница 1: ...ensor offers 360 degree coverage with optimized lens options to accommodate small spaces large spaces and spaces with high ceilings Model Coverage m2 Coverage ft2 E DOC C SR Small Room 41 8 m 2 at 2 4...

Страница 2: ...installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not ins...

Страница 3: ...he back box for connection and to allow slack for future service needs Note Echoflex requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for gr...

Страница 4: ...nting location junction box or finished surface Strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sens...

Страница 5: ...ial from marked access hole c Pull all incoming wires through the access holes of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on...

Страница 6: ...tion on page 8 Note When the sensor is placed into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches...

Страница 7: ...used Sensor actions can be adjusted using the program MODE button See Configuration on page 8 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 3...

Страница 8: ...associated LEDs Custom A sensor that is set for Custom configuration mode DIP switch 2 set to On the default setting can be customized using the ElahoAccess App For more detailed information about cu...

Страница 9: ...ection and manual control can switch the state to occupied When the space is occupied PIR detection and manual control can reset the vacancy timeout Vacancy Timeout Vacancy timeout is the amount of ti...

Страница 10: ...conds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detection...

Страница 11: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Страница 12: ...Echoflex Installation Guide Dual Tech Occupancy Sensor Dual Tech Occupancy Sensor Page 12 of 12 Echoflex...

Отзывы: