Echoflex Installation Guide
Dual Tech Occupancy Sensor
Power Up
All EchoConnect terminations in the system must be made before
applying power to the system and sensor. When the sensor is powered,
the PIR and acoustic detection LEDs illuminate for one minute for
calibration and warm-up, and then return to normal operation according
to the configuration.
Both the PIR and acoustic detection features of the sensor will
automatically adjust the sensitivity threshold to eliminate nuisance
tripping. During this time, configuration is not allowed and no events are
triggered.
Configuration
Basic
MODE button
and LED
AUXILIARY
button
and LED
A sensor that is set for Basic
configuration mode
(DIP switch 2 set to Off) can be
further configured locally
using the other available
DIP switch settings, and the
[MODE] and Auxiliary [A]
buttons and their associated
LEDs.
Custom
A sensor that is set for Custom configuration mode (DIP switch 2 set to
On, the default setting) can be customized using the ElahoAccess App.
For more detailed information about custom configuration options
available, see the ElahoAccess App integrated help system.
Preset
While in Basic configuration mode (DIP switch 2 set to Off), use the
[MODE] and Auxiliary [A] buttons to program the preset that is activated
with an occupancy detected state change. By default, this is Preset 1.
When vacancy is detected, the default action event is Off.
Follow these steps to configure the preset for your sensor:
1. Access the sensor electronics and press and hold the [MODE]
button for three seconds to enter “Program Mode.” The Mode LED
lights in amber to indicate the sensor is in Program Mode and the
Auxiliary LED flashes to indicate the preset number controlled by
the occupancy action. By default, this is Preset 1, therefore the LED
will flash one time, pause two seconds and flash again.
Dual Tech Occupancy Sensor
Page 8 of 12
Echoflex