Echoflex Installation Guide

Dual Tech Occupancy Sensor

DIP Switches

DIP switches on the sensor electronics provide for additional
configuration options including Use Custom Config, Vacancy Timeout,
Enable/Disable detection LEDs, PIR Only Mode, and the ability to restore
the sensor to its factory defaults.

Switch #

Use

1

Unused (leave Off)

2

Enable/Disable Custom Config Mode

• When “Custom Config” is set to On (the default

setting), all other local DIP switch settings are
ignored. Instead, the settings made by the
ElahoAccess App are used.

• When “Custom Config” is set to Off, also known as

Basic configuration mode, the local DIP switch
settings for Vacancy Timeout, Enable PIR LED, and
dual technology features are used. Sensor actions
can be adjusted using the program [MODE] button.
See

Configuration on page 8

.

3 and 4

Vacancy Timeout

• 5 min = Switches 3 and 4 are Off
• 15 min = Switch 3 is Off and Switch 4 is On (default)
• 30 min = Switch 3 is On and Switch 4 is Off
• Auto = Both switches are On

5

Detection LEDs

• When set to On (the default setting), the occupancy

detection LEDs illuminate when movement is
detected.

• When set to Off, the occupancy detection LEDs are

disabled unless the unit is in Walk Test mode.

6

PIR Only Mode

• When set to On, acoustic detection technology is

disabled for the sensor.

• When set to Off (the default setting), both PIR and

acoustic detection technologies are used by the
sensor.

7

Unused (leave Off)

8

Restore to Defaults at boot

• When set to On and power is cycled to the sensor,

the unit restores to its factory default settings.

• Off is the default setting.

Dual Tech Occupancy Sensor

Page 7 of 12

Echoflex

Содержание E-DOC-C-SR

Страница 1: ...ensor offers 360 degree coverage with optimized lens options to accommodate small spaces large spaces and spaces with high ceilings Model Coverage m2 Coverage ft2 E DOC C SR Small Room 41 8 m 2 at 2 4...

Страница 2: ...installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not ins...

Страница 3: ...he back box for connection and to allow slack for future service needs Note Echoflex requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for gr...

Страница 4: ...nting location junction box or finished surface Strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sens...

Страница 5: ...ial from marked access hole c Pull all incoming wires through the access holes of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on...

Страница 6: ...tion on page 8 Note When the sensor is placed into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches...

Страница 7: ...used Sensor actions can be adjusted using the program MODE button See Configuration on page 8 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 3...

Страница 8: ...associated LEDs Custom A sensor that is set for Custom configuration mode DIP switch 2 set to On the default setting can be customized using the ElahoAccess App For more detailed information about cu...

Страница 9: ...ection and manual control can switch the state to occupied When the space is occupied PIR detection and manual control can reset the vacancy timeout Vacancy Timeout Vacancy timeout is the amount of ti...

Страница 10: ...conds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detection...

Страница 11: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Страница 12: ...Echoflex Installation Guide Dual Tech Occupancy Sensor Dual Tech Occupancy Sensor Page 12 of 12 Echoflex...

Отзывы: