12
Installation
Boiler Lining
Burner GL/L-EUF
Boiler lining
The burner lining must be installed at
right angles to the burner tube.
Possible trimming work (bevelling, roun-
ding) as is required for reversing boi-
lers, for example, should done at a
diameter not below 70 % of the combu-
stion chamber diameter.
The space between the flame pipe of
the burner and the boiler lining should
be lined with heat resistant material,
such as Cerafelt.
This space is not allowed to be lined
with brickwork.
D
F
= Combustion chamber diameter
Burnertyp
Dimension A
Dimension T1
φ
D
φ
D1
Standard
100 verl.
200 verl.
E 10
620
720
820
200 - 250
497
525