background image

 

14 

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 

 

IG_GTM

1

1

6

B_

R1

A

 

 

  

G

OLD 

S

ERIES 

GTM116-B T

RANSMITTER

 

a measurable difference! 

EBTRON 

5.6

 

GTM116

 ‐ 

Alarm

 

Features

 

Analog

 

output

 

AO2

 

(OUT2)

 

can

 

be

 

assigned

 

to

 

function

 

as

 

an

 

alarm

 

output.

 

The

 

AO2

 

alarm

 

output

 

can

 

be

 

assigned

 

in

 

the

 

SETUP

 

menu

 

to

 

operate

 

as

 

an

 

alarm

 

for

 

average

 

airflow

 

or

 

pressure

 

depending

 

on

 

MEAS=

 

setting

 

(A02

 

ASGN=ALRM)

 

or

 

as

 

a

 

trouble

 

alarm

 

(AO2

 

ASGN=TRBL)

 

for

 

monitoring

 

the

 

status

 

of

 

the

 

transmitter

 

and

 

sensors.

 

The

 

AO2

 

ASGN=

 

setting

 

is

 

located

 

in

 

the

 

ANALOG

 

OUT

 

submenu

 

of

 

the

 

SETUP

 

menu.

 

The

 

transmitter

 

LCD

 

display

 

will

 

indicate

 

the

 

Alarm

 

status

 

for

 

2

 

seconds,

 

and

 

will

 

cycle

 

through

 

any

 

other

 

alarms

 

if

 

multiple

 

alarm

 

events

 

are

 

active

 

for

 

2

 

seconds

 

each,

 

and

 

then

 

display

 

the

 

current

 

actual

 

flow

 

for

 

2

 

seconds.

 

Detailed

 

set

 

up

 

of

 

the

 

Alarm

 

features

 

is

 

shown

 

in

 

the

 

Setup

 

menu.

 

5.6.1

 

Average

 

Alarm

 

(AO2

 

ASGN=ALRM)

 

AO2

 

output

 

is

 

assigned

 

as

 

an

 

average

 

airflow

 

alarm

 

output.

 

Useful

 

for

 

applications

 

where

 

a

 

low

 

flow

 

alarm,

 

a

 

high

 

flow

 

alarm

 

for

 

operation

 

outside

 

of

 

a

 

defined

 

range

 

(setpoint

 

and

 

tolerance)

 

is

 

required.

 

5.6.2

 

Trouble

 

Alarm

 

(AO2

 

ASGN=TRBL)

 

AO2

 

output

 

is

 

assigned

 

as

 

a

 

transmitter

 

trouble

 

alarm

 

indicating

 

a

 

fault

 

within

 

the

 

transmitter

 

or

 

a

 

sensor

 

of

 

the

 

airflow

 

measurement

 

system.

 

The

 

transmitter

 

LCD

 

will

 

indicate

 

a

 

trouble

 

code

 

and

 

a

 

brief

 

description

 

of

 

the

 

trouble.

 

Contact

 

EBTRON

 

customer

 

service

 

for

 

additional

 

information

 

or

 

assistance

 

with

 

trouble

 

codes.

  

5.6.3

 

No

 

Fault

 

(NO

 

FAULT=HI)

 

When

 

AO2

 

output

 

is

 

assigned

 

as

 

an

 

alarm,

 

this

 

setting

 

configures

 

the

 

normal

 

output

 

condition

 

to

 

be

 

HI

 

or

 

LO

 

relative

 

to

 

the

 

full

 

scale

 

analog

 

output

 

level

 

selected

 

when

 

no

 

fault

 

condition

 

exists.

 

5.6.4

 

Alarm

 

Indications

 

Table

 

7

 

details

 

the

 

alarm

 

types,

 

LCD

 

indications

 

and

 

AO2

 

alarm

 

output

 

indications.

 

User

 

can

 

select

 

either

 

or

 

both

 

of

 

the

 

two

 

Average

 

Alarms

 

or

 

the

 

Trouble

 

Alarm:

 

5.6.5

 

Low

 

Alarm

 ‐ 

“LO

 

ALRM=

 

ON”

 

The

 

Low

 

Alarm

 

is

 

activated

 

when

 

the

 

average

 

airflow

 

falls

 

below

 

a

 

selected

 

set

 

point

 

(SETPNT=)

 ‐ 

tolerance

 

(TOL=)

 

value.

 

Once

 

active,

 

the

 

alarm

 

can

 

be

 

cleared

 

when

 

the

 

average

 

airflow

 

rises

 

above

 

the

 

set

 

point

 ‐ 

tolerance

 

value.

 

5.6.6

 

High

 

Alarm

 ‐ 

“HI

 

ALRM=

 

ON”

 

The

 

High

 

Alarm

 

is

 

activated

 

when

 

the

 

average

 

airflow

 

rises

 

above

 

a

 

selected

 

set

 

point

 

(SETPNT=)

 

+

 

tolerance

  

(TOL=)

 

value.

 

Once

 

active,

 

the

 

alarm

 

can

 

be

 

cleared

 

when

 

the

 

average

 

airflow

 

falls

 

below

 

the

 

set

 

point

 

+

 

tolerance

 

value.

 

5.6.7

 

Trouble

 

Alarm

 ‐ 

“AO2

 

ASGN=TRBL”

 

The

 

Trouble

 

alarm

 

provides

 

trouble

 

codes

 

useful

 

for

 

isolating

 

setup

 

issues

 

or

 

problems

 

within

 

the

 

transmitter

 

or

 

sensors.

 

The

 

transmitter

 

LCD

 

will

 

indicate

 

TROUBLE!

 

regardless

 

of

 

whether

 

AO2

 

is

 

assigned

 

to

 

TRBL.

 

The

 

Diagnostic

 

submenu

 

can

 

be

 

engaged

 

for

 

the

 

error

 

code

 

and

 

a

 

brief

 

description

 

of

 

the

 

trouble.

 

Contact

 

EBTRON

 

customer

 

service

 

for

 

information

 

on

 

troubleshooting

 

using

 

the

 

Trouble

 

error

 

codes.

 

 

 

 

 

 

Table

 

7.

 

GTM116

 

Alarm

 

Types

 

and

 

Notifications

ALARM OUTPUT 

ASSIGNMENT TYPE 

LOCAL LCD DISPLAY OF ALARM 

TYPE AND NOTIFICATION

ANALOG OUTPUT 2 

ALARM INDICATION

NETWORK

ALARM INDICATION

**LOW ALARM**

(Average Alarm)

Display alternates between 

**LOW 

ALARM**

 (then any other alarms) and 

actual reading for 2 seconds each.

**HIGH ALARM**

(Average Alarm)

Display alternates between 

**HIGH 

ALARM**

 (then any other alarms) and 

actual reading for 2 seconds each.

TROUBLE !

(Trouble Alarm)

Display indicates 

TROUBLE ! 

(Refer to DIAGNOSTIC menu to obtain a 
brief description of the error and any 
other alarms).

On alarm or trouble, OUT2 is 
active high (or active low) 
relative to the full scale 
maximum (or minimum) 
analog value as determined 
by the SETUP Menu “NO 
FAULT=” selection. Individual 
sensor velocities can be 
viewed using the Diagnostics 
submenu.

Alarm Status is available at 
BACnet Objects and 
Modbus Registers.  Refer to 
BACnet Objects List and 
Modbus Register Map for 
additional detail.

Содержание Advantage III Gold Series

Страница 1: ...rflow Sensors Combination Ethernet Network Output and Dual Analog Output Document Name IG_GTM116 B_R1B a measurable difference EBTRON BACnet is a registered trademark of ASHRAE ASHRAE does not endorse...

Страница 2: ...TER START UP INITIALIZATION AND SETUP MENUS 11 5 1 Changing the System of Units IP or SI Units 11 5 2 GTM116 Transmitter Calibration 11 5 3 GTM116 LCD Display Notifications 11 5 4 Factory Default Menu...

Страница 3: ...re 4 Type B Transmitter Connector Panel Detail 7 Figure 5 Connector Detail 7 Figure 6 GTM116 Combination Analog Ethernet Transmitter Interior Detail 8 List of Tables Table 1 GTM116 Power Transformer S...

Страница 4: ...in 50 8 mm to each side and 3 5 in 88 9 mm below the transmitter to allow for cover removal sensor connections and heat dissipation Locate the transmitter in a location that can be reached by all conn...

Страница 5: ...ed LCD contrast Transmitter status LED Green 1 second flash normal 2 second flash for fault High accuracy A D converter Gold plated interconnects to optional output cards Positive locking cable recept...

Страница 6: ...VA Req 1 12 5 14 2 13 6 15 3 13 7 15 4 14 8 16 3 2 Connecting Power to the Transmitter Connect 24 VAC power to the large two position power input terminal labeled POWER on the upper right hand side o...

Страница 7: ...de a drip loop at the transmitter if there will be the potential for water runoff or condensation along the bleed sensor cable s Bleed sensor cable plugs are keyed as shown below Line up plug with rec...

Страница 8: ...o wire the analog outputs slide the cover plate up and off of the enclosure Ensure that the power switch is in the OFF position Connect signal wires for airflow rate or equivalent differential pressur...

Страница 9: ...digit address segment that is under change Change the blinking segment by pressing the UP or DOWN buttons to arrive at the desired segment setting Depress the ENTER key to set this segment and to mov...

Страница 10: ...nsert 1 Flow 30019 30020 Insert 4 Flow 4 30021 30028 float F Temperature Traverse 20 to 160 30021 30022 Insert 1 Temp 30027 30028 Insert 16 Temp 4 30029 30030 float Sq Ft Area 0 to 100 4 300202 word F...

Страница 11: ...s are shown in IP System Of Units When SI System of Units is selected the units of measure abbreviations used in the menus is shown in Table 5 IP System of Units Description SI System of Units Descrip...

Страница 12: ...set factor 0 000 0 000 AO2 SGNL Output 2 signal voltage or mA temperature or alarm mA see alarms mA see alarms AO2 MS Output 2 signal minimum scale 20 F 30 C AO2 FS Output 2 signal full scale 160 F 70...

Страница 13: ...desired the output can be set to provide standard airflow measurement units displayed as SCFM and SFPM which provides measurements that are corrected to standard conditions 5 5 4 Output Scaling EBTRON...

Страница 14: ...and AO2 alarm output indications User can select either or both of the two Average Alarms or the Trouble Alarm 5 6 5 Low Alarm LO ALRM ON The Low Alarm is activated when the average airflow falls belo...

Страница 15: ...ntrol system To set a fixed output signal for airflow and temperature navigate to the OUTPUT TEST submenu in the TOOLS menu OUT1 and OUT2 tests are independently accessed and the output will maintain...

Страница 16: ...odbus networks or via EB Link Reader Airflow and temperature of individual sensors can be read across BACnet or Modbus networks or downloaded directly to an EB Link Reader if the infra red EB Link opt...

Страница 17: ...cters for blank or unwanted text EXT CABLE 0 SET EXT CABLE EXT CABLE 0 LCD TRBL ON Set measurement mode to AIRFLOW MEAS PRESS LCD DSPL BOTH SETUP Instruction text USE AND ENT then NAME _ GENERAL SET O...

Страница 18: ...ate this setting is fixed and cannot be modified AO1 ASGN iWG AO1 UM FIXED The text AO1 UM FIXED flashes to indicate that this setting is fixed and cannot be modified ANALOG OUT AO1 ASGN FLOW SET AO1...

Страница 19: ...ve to right and ESC to move to left Set network device instance number Set network protocol type Enter gateway IP address use up down arrow buttons to select value and press ENT to move to right and E...

Страница 20: ...low alarm setpoint Units based on ALARM UM DELAY 2 MIN SET DELAY DELAY 2 MIN Enter alarm delay RESET AUTO SET RESET RESET AUTO Set alarm RESET AUTO will clear once the alarm is not active MANUAL requi...

Страница 21: ...Adjust Wizard will now be engaged as outlined in the following steps The GAIN and OFF values will be updated and PRESS ADJ ON will be set if the wizard is successfully completed OF PRESS 2 OUT2 TEST...

Страница 22: ...RESET ADJ NO RESET ALL NO Sets security level to MED In this mode a user defined code is specified In the event of loss of code contact EBTRON for a unique code for this transmitter to unlock and rese...

Страница 23: ...te 2 L2 L1 POWER 24VAC IN OUT 1 AIRFLOW PRESSURE OUTPUT SIGNAL 1 2 COM ANALOG OUTPUT OUT 2 TEMP OR ALARM OUTPUT SIGNAL ANALOG BAS INTERFACE OUT 2 can be set as an analog Temperature Alarm or Trouble o...

Страница 24: ...1663 Hwy 701 S Loris SC 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 Internet EBTRON com IG_GTM116 B_R1A GOLD SERIES GTM116 B TRANSMITTER a measurable difference EBTRON a measurable differen...

Отзывы: