6A

6B

Enter code and confirm code (NOTE: if LOCK SEC= HIGH, DO NOT lose code!)

Clears all disabled trouble settings

1: NO PROBES

(example shown)

Displays unit serial number.

Displays main PCB serial number.

For sensors =1 to 9, A to G (number of sensors dependant on sensor type).

For sensors =1 to 9, A to G (number of sensors dependant on sensor type).

For sensors =1 to 9, A to G (number of sensors dependant on sensor type).

Enable/disable security lock.

Resets network settings to factory default.

O

O

FROM PART
5 'A'

Displays probe serial numbers followed by a T if connected and functioning properly, and 
then followed by an F if not connected or not functioning properly.

SERIAL NUMBERS

C1 ######  

C2 ######  

1: NO PROBES

(example shown)

FROM PART
5 'B'

SENS VOLTS

1=H##.## T##.## 

1=##.#F    

RESET ADJ

BRD #####  

SENS VELOCITY 

1=#####FPM   

SENS TEMP  

C3 ######  

C4 ######  

DIAGNOSTICS

UNIT #######  

TRBL CODES

*LOCK=OFF

SECURITY

*LOCK SEC=LOW

DSBL TRBL CODE?

ARE YOU SURE?

DSBL TRBL=NO

DSBL TRBL=YES

ARE YOU SURE?

RESET TRBL=YES

RESET TRBL=NO

Reset Flow/Pressure adjustments to GAIN = 1, OFF = 0, FLOW/PRESS ADJ = OFF

RESET NET=YES

LOCK SEC=MED

RESET ADJ=NO

RESET ALL=NO

Sets security level to MED.  In this mode, a user defined code is specified.  In the event of loss 
of code, contact EBTRON for a unique code for this transmitter to unlock and reset code.

RESET SENS=NO

RESET ADJ=YES

LOCK=ON

ENTR CODE:0

CONF CODE:0

TRBL HISTORY

RESET

RESET ALL

ARE YOU SURE?

RESET NET=NO

RESET NET

RESET ALL=YES

RESET SENS

ARE YOU SURE?

RESET SENS=YES

ARE YOU SURE?

LOCK SET=HIGH

SET LOCK?

LOCK=OFF

SET LOCK SEC?

LOCK SEC=LOW

Sets security level to LOW.  In this mode, there is no prompt for a lock code.  
The last 4 digits of the board serial are used to unlock.

Sets security level to HIGH.  In this mode, a user defined code is specified.  In the event of loss 
of code, transmitter must be returned to EBTRON for unlock / reset.

Reset sensor data, transmitter resets after completion

Reset ALL changes back to factory defaults.  Transmitter resets after completion.

PROBE TYPE 

TYPE= B

Type 'B' for Bleed sensors.

GTC, GTM models only

Displays active trouble codes and their descriptions.  Contact EBTRON customer service for 
recommended service information. 

Set DSBL TRBL= YES to ignore currently displayed TRBL alarm.  To disable all trouble codes, 
see SETUP -> DISPLAY -> LCD TRBL.

Displays historical list of last 5 trouble codes encountered and their descriptions.  
Note that spurious trouble codes may self-clear during normal operation, and this feature permits viewing them even after they have resolved. 

RESET TRBL SET

Содержание Advantage III Gold Series

Страница 1: ...rflow Sensors Combination Ethernet Network Output and Dual Analog Output Document Name IG_GTM116 B_R1B a measurable difference EBTRON BACnet is a registered trademark of ASHRAE ASHRAE does not endorse...

Страница 2: ...TER START UP INITIALIZATION AND SETUP MENUS 11 5 1 Changing the System of Units IP or SI Units 11 5 2 GTM116 Transmitter Calibration 11 5 3 GTM116 LCD Display Notifications 11 5 4 Factory Default Menu...

Страница 3: ...re 4 Type B Transmitter Connector Panel Detail 7 Figure 5 Connector Detail 7 Figure 6 GTM116 Combination Analog Ethernet Transmitter Interior Detail 8 List of Tables Table 1 GTM116 Power Transformer S...

Страница 4: ...in 50 8 mm to each side and 3 5 in 88 9 mm below the transmitter to allow for cover removal sensor connections and heat dissipation Locate the transmitter in a location that can be reached by all conn...

Страница 5: ...ed LCD contrast Transmitter status LED Green 1 second flash normal 2 second flash for fault High accuracy A D converter Gold plated interconnects to optional output cards Positive locking cable recept...

Страница 6: ...VA Req 1 12 5 14 2 13 6 15 3 13 7 15 4 14 8 16 3 2 Connecting Power to the Transmitter Connect 24 VAC power to the large two position power input terminal labeled POWER on the upper right hand side o...

Страница 7: ...de a drip loop at the transmitter if there will be the potential for water runoff or condensation along the bleed sensor cable s Bleed sensor cable plugs are keyed as shown below Line up plug with rec...

Страница 8: ...o wire the analog outputs slide the cover plate up and off of the enclosure Ensure that the power switch is in the OFF position Connect signal wires for airflow rate or equivalent differential pressur...

Страница 9: ...digit address segment that is under change Change the blinking segment by pressing the UP or DOWN buttons to arrive at the desired segment setting Depress the ENTER key to set this segment and to mov...

Страница 10: ...nsert 1 Flow 30019 30020 Insert 4 Flow 4 30021 30028 float F Temperature Traverse 20 to 160 30021 30022 Insert 1 Temp 30027 30028 Insert 16 Temp 4 30029 30030 float Sq Ft Area 0 to 100 4 300202 word F...

Страница 11: ...s are shown in IP System Of Units When SI System of Units is selected the units of measure abbreviations used in the menus is shown in Table 5 IP System of Units Description SI System of Units Descrip...

Страница 12: ...set factor 0 000 0 000 AO2 SGNL Output 2 signal voltage or mA temperature or alarm mA see alarms mA see alarms AO2 MS Output 2 signal minimum scale 20 F 30 C AO2 FS Output 2 signal full scale 160 F 70...

Страница 13: ...desired the output can be set to provide standard airflow measurement units displayed as SCFM and SFPM which provides measurements that are corrected to standard conditions 5 5 4 Output Scaling EBTRON...

Страница 14: ...and AO2 alarm output indications User can select either or both of the two Average Alarms or the Trouble Alarm 5 6 5 Low Alarm LO ALRM ON The Low Alarm is activated when the average airflow falls belo...

Страница 15: ...ntrol system To set a fixed output signal for airflow and temperature navigate to the OUTPUT TEST submenu in the TOOLS menu OUT1 and OUT2 tests are independently accessed and the output will maintain...

Страница 16: ...odbus networks or via EB Link Reader Airflow and temperature of individual sensors can be read across BACnet or Modbus networks or downloaded directly to an EB Link Reader if the infra red EB Link opt...

Страница 17: ...cters for blank or unwanted text EXT CABLE 0 SET EXT CABLE EXT CABLE 0 LCD TRBL ON Set measurement mode to AIRFLOW MEAS PRESS LCD DSPL BOTH SETUP Instruction text USE AND ENT then NAME _ GENERAL SET O...

Страница 18: ...ate this setting is fixed and cannot be modified AO1 ASGN iWG AO1 UM FIXED The text AO1 UM FIXED flashes to indicate that this setting is fixed and cannot be modified ANALOG OUT AO1 ASGN FLOW SET AO1...

Страница 19: ...ve to right and ESC to move to left Set network device instance number Set network protocol type Enter gateway IP address use up down arrow buttons to select value and press ENT to move to right and E...

Страница 20: ...low alarm setpoint Units based on ALARM UM DELAY 2 MIN SET DELAY DELAY 2 MIN Enter alarm delay RESET AUTO SET RESET RESET AUTO Set alarm RESET AUTO will clear once the alarm is not active MANUAL requi...

Страница 21: ...Adjust Wizard will now be engaged as outlined in the following steps The GAIN and OFF values will be updated and PRESS ADJ ON will be set if the wizard is successfully completed OF PRESS 2 OUT2 TEST...

Страница 22: ...RESET ADJ NO RESET ALL NO Sets security level to MED In this mode a user defined code is specified In the event of loss of code contact EBTRON for a unique code for this transmitter to unlock and rese...

Страница 23: ...te 2 L2 L1 POWER 24VAC IN OUT 1 AIRFLOW PRESSURE OUTPUT SIGNAL 1 2 COM ANALOG OUTPUT OUT 2 TEMP OR ALARM OUTPUT SIGNAL ANALOG BAS INTERFACE OUT 2 can be set as an analog Temperature Alarm or Trouble o...

Страница 24: ...1663 Hwy 701 S Loris SC 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 Internet EBTRON com IG_GTM116 B_R1A GOLD SERIES GTM116 B TRANSMITTER a measurable difference EBTRON a measurable differen...

Отзывы: